Frico sirefa Original Instructions Manual page 14

Sire advanced fan heater - water
Table of Contents

Advertisement

GB
Control with mixing cabinet, with falling outlet
temp
Comfort:
1. Opens the valve gradually to fully open
valve.
2. Gradually closes damper to night mode
3. Slows down the fan.
Eco:
1. Gradually closes damper to night mode
2. Opens the valve gradually to full heating.
3. Slows down the fan.
Max. outlet temp. limit +32°C.
Heating step diff.
When the temperature falls below the set
point value the fan speed increases (the high
speed limit is position 4). Which temperature
difference the speed is to be increased by a
step for is selected in Heating step diff.
>Installer menu>Heating
settings
Eco / Comfort
Heating step limit
Sensor calibration
Factory setting
Heating step diff.: 1.0 K (-10 K – 10 K)
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
>Installer menu>Heating
settings
Heating step diff.
Sensor calibration
Control range limit
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)
34
SIRe Advanced Fan Heater Water
>Installer menu>Heating
settings
Heating step limit
1.0 K
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
0.0 K
Return water temp.
If there is a demand for the temperature
of the return water not to exceed a certain
value, this function is activated under Return
water temp. A return water temperature
sensor (proximity sensor SIReWTA, option)
must then be installed on the return water
pipe.
Install Return temp. Sensor to Connected
and select max return temperature (15-90 °C)
using the turn wheel. During operation, this
function limits the valve's degree of opening,
which reduces the flow and the return
temperature.
>Installer menu>Heating
settings
Sensor calibration
Return water temp.
Stepless heat control
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Factory setting
Return temp. sensor: Not connected
(Connected)
Return temp. limit: Off (15 – 90°C)
Stepless heat control
To use Advanced fully, stepless heat control
must be used.
>Installer menu>Heating
settings
Return water temp.
Stepless heat control
Control range limit
Factory setting
Stepless heat control: ON (Off - not
selectable)
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Not connected
Connected
Installer menu>Heating
settings>Return water temp.
Return temp. limit
OFF
>Installer menu>Heating
settings
Stepless heat control
ON

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirefawm

Table of Contents