Page 1
Original instructions SIRe Advanced Fan Heater - Water With quick guide SIReFA SIReFAWM ..62 ..22 ..42 ..2 ..82 ..102 ..122 ..142 ..162 ..182 For wiring diagram, please see last pages.
SIRe Advanced Fan Heater Water Quick guide/start up Wiring diagrams The wiring diagrams are in a separate section Check that all constituent parts are present (see section Constituent parts). at the end of this manual. When external PC board Base SIReB1X is Advice about location used, wiring between the PC board base and the unit must be done.
SIRe Advanced Fan Heater Water Start up Unit with mixing cabinet System supplied with power. At the first start When a mixing cabinet is used the supplied up, the start-up wizard is run and the basic Return temp. sensor SIReWTA must be settings are made.
Enter ID/Operation without control unit Start up Unit with mixing cabinet Start up Jumper settings Constituent parts SIReFA (without mixing cabinet) SIREFAWM (with mixing cabinet) Operating modes Operating modes (without mixing cabinet) Operating modes (with mixing cabinet) Control unit SIReUA1...
SIRe Advanced Fan Heater Water Constituent parts SIReFA (without mixing cabinet) Integrated in fan heater SIReIT, internal SIReUA1, Wall unit cover SIReB1, temperature control unit integrated PC sensor Competent and Board Base Advanced SIReOTX, SIReCC, SIReA1X, outdoor temperature modular cable...
SIRe Advanced Fan Heater Water SIREFAWM (with mixing cabinet) SIReB1, integrated SIReIT, internal SIReUA1, Wall unit cover PC Board Base temperature control unit sensor Competent and Advanced SIReA1X, SIReOTX, SIReWTA, SMM24, PC board HUB outdoor clamp-on sensor damper motor SIReCC, Advanced temperature modular cable...
Page 7
SIRe Advanced Fan Heater Water Option SIReCJ6, SIReWTA, SIReRTX, external SIReUR, kit SIReCJ4, SIReCC, joint piece clamp-on sensor room temperature for recessed joint piece modular cable sensor installation Type RSK-no. E-no. Description HxWxD SIReRTX 673 09 22 87 510 12 External room temperature sensor 70x33x23 SIReUR*...
Page 8
SIRe Advanced Fan Heater Water Water control - valve kit SDM24 TBVCM Water control - option VMOP SDM24 TBVCMP VAT, adjustment tool for valve package. SDM24 TRVS Type RSK-no. Description Connection VMO15LF 673 09 47 Modulating DN15 VMO15NF 673 09 48 Modulating DN15 VMO20...
SIRe Advanced Fan Heater Water Operating modes Operating modes (with mixing cabinet) Operating modes (without mixing cabinet) The control is based on two operating modes: Control is based on the four operating modes: • Auto Thermostat / Manual fan • Thermostat / Manual fan Manual •...
SIRe Advanced Fan Heater Water Control unit SIReUA1 Overview Statuswindow (Auto mode) °C °C Statuswindow Statuswindow (Manual mode) 19 .0 -5.0 °C °C Back arrow Forward arrow Rotary dial Fan speed step Heating step Meny Week program Alarm Red led Week program Run signal Night...
SIRe Advanced Fan Heater Water Main menu System on/off Switch the whole unit off manually. In Off the Current settings display goes out; as soon as a button is pushed Displays set room temp, high speed limit and the display lights and shows System on/off. To week program status.
SIRe Advanced Fan Heater Water Installer menu To check which days a certain program is active, select a week day by pressing the To enter the Installer menu, code 1932 is forward arrow, the program is marked and entered. Select the digits using the rotary dial those days that the program is used will be and confirm using the forward arrow.
SIRe Advanced Fan Heater Water Week program is activated by selecting On, Stepless fan control under Week program on/off. In On-mode, Settings for stepless fan control. a sun, moon or Off in the Status window Fan control can be controlled in 5 steps or appears to indicate day, night respectively steplessly through external steering from Off-function.
Page 14
SIRe Advanced Fan Heater Water Control with mixing cabinet, with falling outlet temp Return water temp. Comfort: If there is a demand for the temperature of the return water not to exceed a certain 1. Opens the valve gradually to fully open value, this function is activated under Return valve.
SIRe Advanced Fan Heater Water Control range limit External filter guard The maximum room temperature that a user If an external filter guard, e.g. a pressure can select is limited to between 5 – 35°C. switch, is used, it is activated under External filter guard, select On.
SIRe Advanced Fan Heater Water Day damper pos. External control (BMS) Desired current damper position daytime. BMS functions can be activated under External control. >Installer menu>Mixing >Installer menu>Mixing cabinet cabinet Min outlet temp. Activate External on/off (5-30V AC/DC from Day damper pos. Day damper pos.
User reset (Room temp. day resp. night, high speed limit) to factory setting. Service menu >Installer menu>General >Installer menu>User reset settings Execute user reset? The service menu is password protected and Function test is used for support in contact with Frico or User reset authorised installer.
Overheat protection authorised installer or Frico. The overheat protection is designed to limit the temperature of the heater to a maximum of +90° C. If the temperature should exceed 95°C e.g.
Page 19
SIRe Advanced Fan Heater Water Table - Alarm Alarm Cause Action Motor Thermal switch has deployed. Check that nothing is obstructing the alarm One or several motors have unit’s air intake and exhaust. When the overheated. (Only units with overheated motor has cooled the thermal withdrawn thermal switches.) switch shuts again and the alarm can be reset.
Page 20
(see the Settings heating section) Internal sensor faults Fault on or missing internal Check connection of the sensor. If sensor in the unit. there is no sensor, contact Frico for support. ID Error Two or more SIReB1(X) in Contact Frico for support.
Page 21
SIRe Advanced Fan Heater Water Connecting external control - including BMS functions SIReA1X RPM indication Heating indication Outdoor temp. sensor External night reduction External alarm IN Ext. speed ctrl. 0-10V DC IN Ext. Heating control 0-10V DC IN External ON/OFF ALARM OUT (BMS) RPM indication Operation indication OUT (BMS)
Page 24
SIRe Advanced Fan Heater Water BMS INDICATION OUT (potential free contact max 3A, 230V) ALARM OUT (BMS) (potential free contact, max 3A, 230V) EXTERNAL ON/OFF, 5-30V AC/DC EXTERNAL HEAT 0-10V DC IN EXTERNAL RPM 0-10V DC IN EXTERNAL ALARM IN (potential free contact) EXTERNAL SETBACK TEMP.
Page 25