SIGNAL OUTPUT module MS

The signal conditioner provides two different analog output
signals, both proportional to the signal input.
Output in Current : 4 to 20 mA, terminals 9 - 10
Output in Voltage : 0 to 10 Vdc, terminals 11 - 12
Do not use both outputs simultaneously. Only one selection
can be made.
The side label shows which one is selected.

CHANGING THE SIGNAL OUTPUT

All signal conditioners are delivered as a standard version, with the analog output selected as
4 to 20 mA, unless specified otherwise. To select a 0 to 10 V output, remove jumpers E and
F as shown in Figure 6. Other non-standard output voltage and current ranges may be obtained
by adding and/or replacing resistors given in Tables 2 and 3.
NON STANDARD OUTPUT
VOLTAGES
Output
Value in K for :
in V.
R29
R30
±10
49.9
-----
0 to 1
-----
-----
0 to 5
-----
-----
1 to 5
-----
100
E
R18
R29
R30
R24 R25 R31 R32
TABLE 2
R31
R32
200
----
11
100
100
100
66.5
100
"-----" means "Resistor must not be installed"
Jumpers E and F : Closed only if the output is 4 to 20 mA.
F
NON STANDARD OUTPUT
CURRENTS
Output
Value in
in mA.
R18
0 to 5
-----
0 to 10
-----
1 to 5
100 K
0 to 20
-----
Replace or add the indicated
resistors with the values shown
in Tables 2 and 3 for the desired
output.
FIG.6