Setup Examples

Example #1: Use of the OFFSET Parameter

Setup for a 4-20ma transducer signal corresponding to 0-500 gallons of fluid (reading in 10th of a gallon resolution):

Example #2: Use of the LOW SCALE Parameter

Setup for a 4-20ma transducer signal corresponding to 500-2000 degrees Fahrenheit temperature i.e. 500 degrees at 4ma
and 2000 degrees at 20ma (one degree resolution):

Example #3: Use of the TARE Parameter

Setup for a 0-5Vdc transducer signal corresponding to 0-10.00 pounds of material being packaged in a box weighing 0.50
pounds with display reading in 0.01 lb. increments. DSP3200 should display the weight of the material only (not the box
as well):

SYSTEM CONFIGURATION

After entering the correct pass-code and selecting the blinking 'SYS' (ref. SETUP section), DPS3300 Series goes into
SYSTEM CONFIGURATION mode. This mode allows setting up parameters
that affect all the channels or the instrument in general.

Setup For Display Options

After pushing SETUP key while SYS is blinking, the display briefly shows
'dSP OPt' (for display option) and then the present Display Option setting.
Table 3 below lists all 6 display options available. Use
thru the options. Once the desired Display Option is shown, push SETUP key
to enter the setting and go to Setup For Display Time.

Table 3. Display Options

DISPLAY OPTION
1) Display elapsed time
2) Scan active channels
3) Display channel with highest reading
4) Display channel with lowest reading
5) Display deviation from SETPOINT
6) Display channel differential
DECIMAL POINT
HIGH SCALE
LOW SCALE
OFFSET
TARE
DECIMAL POINT
HIGH SCALE
LOW SCALE
OFFSET
TARE
DECIMAL POINT
HIGH SCALE
LOW SCALE
OFFSET
TARE
= 999.9
= 500.0
= 000.0
= 4.000
= 0.000
= 9999
= 2000
= 500
= 4.00
= 0.000
= 99.99
= 10.00
= 00.00
= 0.00
= 0.50
DIG
key to step
DISPLAY WINDOW READS
ELPSEd t
SCAn
HI CHAN
LO CHAN
dSP dEN
CH1 dIF