How to Reset and Program Thermocouple Type (or RTD)

How to Reset and Program Thermocouple Type (or RTD)
A DPS3301-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be
A DPS3301-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be
programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under
programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under
'SETUP'). Alternately, a thermocouple/RTD may be selected by turning On power to the unit while holding
'SETUP'). Alternately, a thermocouple/RTD may be selected by turning On
in the appropriate key (see Figure 1). This procedure also clears the memory and programs factory defalult
values for limits, rate timebase etc. Therefore, after performing Power-up reset, various parameters such as
limits, rate time base etc., must be re-programmed to a desired value. However, if done in SETUP mode, no
programmed parameters such as limits, Timers etc. are erased from the memory. It is recommended that
thermocouple (RTD) selection be done in SETUP. Power-up reset should be performed if it is suspected that
program memory may have been corrupted due to power surge, noise on electrical lines etc.
FIGURE 1. Thermocouple/RTD Selection Keys
E t/c
Memory Clear only

DISPLAY MODES

The DPS3301 can be programmed to display in any one of the following modes:
Mode
PROCESS
SETPOINT DEVIATION
INSTANTANEOUS RATE
PROCESS HIGH
PROCESS LOW
ELAPSED TIME
TIMER 1 COUNT DOWN
TIMER 2 COUNT DOWN
SCAN
K t/c, RTD392,
Thermistor
T t/c
J (R, S or B) t/c,
RTD385
Display
Description
PrOCESS
SP. DEVN
In. rAtE
Pr. HIGH
Pr. LO
ELPSd. T
tr1. Cnt
tr1. Cnt
SCAn
Page
KEY
HI/LO
C/F
ALARM
TIMER
RESET
.
NOTE: All keys, except RESET, clear
memory and program necessary factory
default values. RESET key clears memory
only and programs no default values.
However, previous thermocouple type is
retained.
Displays process value.
Displays setpoint deviaition.
Displays Instantaneous rate value.
Displays process' highest reading
Displays process' lowest reading
Displays elapsed time.
Display Timer 1 count down value
Display Timer 2 count down value
Scans through all the above parameters
6
Input Type Selected
J (R, S or B , RTD 385)
Thermistor
K (RTD 392)
T
E
Memory cleared – no
factory default values
programmed.