Summary of Contents for Lennox CLIMATIC 200

  • Page 1: User Manual

    User manual CLIMATIC™ 200/400 - Controller Providing indoor climate comfort MUL35E-0506 09-2006...
  • Page 2 INDEX • INDEX • GENERAL DESCRIPTION ® • THE KEYPAD, Climatic ® • THE KEYPAD, Climatic ® • THE KEYPAD REMOTE CONTROLLER (OPTION), RC Climatic ® • THE KEYPAD REMOTE CONTROLLER (OPTION), RC Climatic • FUNCTION UNIT COMMISSIONING SELECTING OPERATING MODE SELECTING SET POINT •...
  • Page 3: General Description

    GENERAL DESCRIPTION This equipment is an electronic device that controls packaged water cooling systems via air and reversible air/water heat pumps: (EAC/EAR 0251SM to 1804SM). The thermostat allows the following operations: - Unit ON/OFF. - Select system operating mode. - Set point adjustment. - Alarm signal relay.
  • Page 4 THE KEYPAD INCORPORATED AT THE UNIT, MODEL Climatic ® This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment. - Cooling set point, cooling differential temperature.
  • Page 5 THE KEYPAD INCORPORATED AT THE UNIT, MODEL Climatic ® This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment. - Cooling set point, cooling differential temperature.
  • Page 6 THE KEYPAD REMOTE CONTROLLER (OPTION), MODEL RC Climatic ® This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment. - Cooling set point, cooling differential temperature.
  • Page 7 THE KEYPAD REMOTE CONTROLLER (OPTION), MODEL RC Climatic ® This is a 3-digit display, the inlet water temperature is shown in degrees (default), ºC (when shows decimal point). The following can also be displayed: - Values of all parameters controlled by the equipment. - Cooling set point, cooling differential temperature.
  • Page 8 FUNCTION When all the instructions in the Operating, Service and Installation Manual have been carried out, the unit can be commissioned as follows: - Set the general cut-off switch to ON. - Pressing button lets you turn ON the unit. The display lights up and shows the on off inlet water temperature, or an alarm indication, and the different leds on the unit will flash (see page 16 for alarm section).
  • Page 9 MENU MODE Press buttons and , to enable the user mode on off to get to the menu mode Press buttons simultaneously and mode on off Press buttons simultaneously mode on off When the leds on the display flash alternatively from one to the other, you are on menu mode.
  • Page 10 SET POINT THERMOSTAT FUNCTION DESCRIPTION LEVEL 1 LEVEL 2 LEVEL 3 MAIN DISPLAY Set point value Cooling set point It shows: SET POINT Inlet water temperature Active alarms Set point value Heating set point See page 7, for adjustment of set point of the system. The water temperature is thermostatically controlled via a set point and a tolerance range (differential).
  • Page 11 ANALOGUE INPUTS MAIN DISPLAY It shows: SET POINT Inlet water temperature Probe value Active alarms mode Probe value on off Probe status Probe value Probe value Probe value When the leds on the display flash alternatively from one to the other, you are on menu mode.
  • Page 12 OPTIONS Remove the wire between 93 and 94 terminal block on the electrical box and insert a contact. If the unit stops with ON/OFF Remote, "E00" will appear on the unit display. On heat pump units, it is possible to select cooling or heating mode with a remote contact. The ON/OFF remote can be combined with this function in order to control the unit from a long distance, with the Off/Cool/Heat options.
  • Page 13 OPTIONS Set point ºC Set point ºC 12ºC 42ºC heating set point 9ºC 38ºC cooling set point outdoor temp. ºC outdoor temp. ºC 6ºC 12ºC 25ºC 35ºC starting starting differential differential Dynamic Dynamic set point set point 6ºC -10ºC (only for heat pump units) When the outdoor temperature exceeds 35ºC, the unit set When the outdoor temperature is 6ºC the unit set point is point is the set value.
  • Page 14 MODIFY PARAMETERS MAIN DISPLAY mode on off It shows: Inlet water temperature Active alarms mode on off PARAMETERS When the leds on the display flash alternatively from one to the other, you are on menu mode. Menu of configuration parameters of the unit. General configuration parameters of the unit (Values (H)).
  • Page 15 MODIFY UNIT PARAMETERS MAX: Maximum value for the parameter. MIN: Minimum value for the parameter. DEF: The default value, factory set. UNIT: The units of measure used. VAR.: Minimum variation allowed. MIN MAX UNIT VAR. ® 25.5 ºC Cooling thermal regulator hysteresis 25.5 ºC Heating thermal regulator hysteresis...
  • Page 16 OPERATING HOURS mode on off It shows: Inlet water temperature Active alarms Compressor 1 operating hours Compressor 2 operating hours mode Compressor 3 operating hours on off Compressor 4 operating hours OPERATING HOURS Water pump operating hours When the leds on the display flash alternatively from one to the other, you are on menu mode.
  • Page 17 ALARM CODES MENU STRUCTURE LEVEL 1 MAIN DISPLAY It shows: SET POINT Inlet water temperature Active alarms Probe status mode LEVEL 2 on off Active alarms Codes ALARMS The unit self-protects through safety devices; when any of these safety devices detect an anomaly, this is shown in the display in order to advise the operator.
  • Page 18 ALARM CODES VIS. DESCRIPTION ACTION EFFECT Anti-freeze alarm. Reset and check: It indicates the outlet water temperature is lower • Check the water filter. than +3ºC (it kit low water temperature is not • Check water flow. Unit stops AUTO/ fitted).
  • Page 19 ALARM CODES VIS. DESCRIPTION EFFECT ACTION Check: Compressor 1 circuit 2 thermal protection alarm: • Check refrigerant charge. Compressor 1 - Compressor thermal protection open. • Check the refrigerant circuit is not blocked. circuit 2 - Faulty power supply. • Check connections and protections. stops •...
  • Page 20 DESCRIPTION OF THE DEFROSTING SYSTEM The defrosting process is activated during heating mode in heat pump units, when the outside temperature is low and the outdoor coil could become frozen. To melt the ice the defrosting function will switch the unit to cooling operation for a short period. During defrosting mode the low pressure is at minimum level, consequently the pressure switch is disabled in this mode.
  • Page 21: Fan Speed Control

    FAN SPEED CONTROL (only for 0091 to 0812 units) It is managed by a fan speed control printed plate located at the electrical box of the unit. The function of the fan speed control is to prevent very low condensing temperatures during cooling mode operation between 0ºC and 46ºC outside temperatures.
  • Page 22 SAFETY DEVICES The units contain various safety devices to avoid damage to the unit due to very low water temperatures. This protection is activated by the control of the unit when the outlet water temperature probe (St2), located inside the water exchanger, measures +5ºC and deactivates when the outlet water temperature probe reaches to +6ºC again.
  • Page 24 BELGIUM, LUXEMBOURG RUSSIA Due to Lennox’s ongoing commitment to quality, www.lennoxbelgium.com www.lennoxrussia.com the Specifications, Ratings and Dimensions are subject to change without notice and without incurring liability. CZECH REPUBLIC SLOVAKIA Improper installation, adjustment, alteration, www.lennoxczech.com www.lennoxdistribution.com service or maintenance can cause property damage or personal injury.