Error Detection; Indoor Unit Remote Control - Fujitsu AGU15RLF Service Manual

Floor type
Hide thumbs Also See for AGU15RLF:
Table of Contents

Advertisement

ER R OR D ETEC TION
INDOOR UNIT
REMOTE CONTROL
If you use a wireless remote control, the lamp
on the photo detector unit will output error codes
by way of blinking patterns.
If you use a wired remote control, error codes
will appear on the remote control display.
See the lamp blinking patterns and error codes
in the table.
An error display is displayed only during operation.
TIMER
OPERATION
ECONOMY
TIMER lamp
OPERATION
ECONOMY
(orange)
lamp (green)
lamp (green)
Wired remote control display (Option)
If an error occurs, the following display will be shown.
("Er" will appear in the set room temperature display.)
Error code
: 0.5s on / 0.5s off
: 0.1s on / 0.1s off
( ) : Number of flashing
2013.10.10
Wired
Lamps
remote
OPERATION TIMER ECONOMY
control
(1)
(1)
(1)
(2)
(1)
(5)
(2)
(1)
(2)
(2)
(2)
(3)
(2)
(4)
(2)
(7)
(3)
(2)
(3)
(5)
(4)
(1)
(4)
(2)
(5)
(1)
(5)
(3)
(5)
(7)
(5)
(15)
(6)
(2)
(6)
(3)
(6)
(4)
(6)
(5)
Description
OPERATION TIMER ECONOMY
Serial communication error
(6)
Wired remote control
(7)
communication error
Check run unfinished
(7)
Unit number or Refrigerant
(7)
circuit address setting error
[Simultaneous Multi]
(7)
Indoor unit capacity error
(7)
Combination error
(7)
• Connection unit number
error (indoor slave unit)
[Simultaneous Multi]
(7)
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
(8)
Master unit, slave unit set-up
error [Simultaneous Multi]
Indoor unit PCB model
(8)
information error
Manual auto switch error
(8)
Room temp. sensor error
(8)
Indoor unit Heat Ex. Middle temp.
sensor error
(9)
Indoor unit fan motor error
(9)
Drain pump error
(9)
Damper error
(9)
Indoor unit error
(10)
Outdoor unit main PCB model
information error or
(10)
communication error
Inverter error
(10)
Active filter error, PFC circuit error
(10)
Trip terminal L error
(13)
12
Wired
Lamps
remote
Description
control
Display PCB microcomputers
(10)
communication error
Discharge temp. sensor error
(1)
Compressor temp. sensor error
(2)
Outdoor unit Heat Ex. liquid
(3)
temp. sensor error
Outdoor temp. sensor error
(4)
Suction Gas temp. sensor error
(5)
2-way valve temp. sensor error
(6)
3-way valve temp. sensor error
Heat sink temp. sensor error
(7)
Sub-cool Heat Ex. gas inlet
temp. sensor error
(2)
Sub-cool Heat Ex. gas outlet
temp. sensor error
Liquid pipe temp. sensor error
(3)
Current sensor error
(4)
Discharge pressure sensor error
Suction pressure sensor error
(6)
High pressure switch error
Trip detection
(4)
Compressor rotor position
(5)
detection error
Outdoor unit fan motor error
(7)
4-way valve error
(9)
Discharge temp. error
(1)
Compressor temp. error
(3)
High pressure error
(4)
Low pressure error
(5)
Branch boxes error
(2)
[Flexible Multi]