Specifications - Fujitsu ASYG24LFCA Service Manual

Wall mounted type
Hide thumbs Also See for ASYG24LFCA:
Table of Contents

Advertisement

SP E C IF ICAT ION S
ELECTRICAL DATA
TYPE
INDOOR UNIT
OUTDOOR UNIT
COOLING CAPACITY
HEATING CAPACITY
POWER SOURCE
FREQUENCY
COOLING
RUNNING
CURRENT
HEATING
COOLING
INPUT WATTS
HEATING
E.E.R.
COOLING
COP
HEATING
MOISTURE REMOVAL
AIR CIRCULATION HIGH
COOLING
MAXIMUM
CURRENT
HEATING
FAN MOTOR
POWER SOURCE
INDOOR UNIT
(Cool)
INDOOR UNIT
(Heat)
OUTDOOR UNIT (Cool)
OUTDOOR UNIT (Heat)
2011.01.20
Cool & heat inverter
ASYG24LFCA
AOYG24LFL
7.10 kW
8.00 kW
230 V
50 Hz
9.7 A
9.7 A
2.20 kW
2.21 kW
3.23 kW/kW
3.61 kW/kW
2.7 L/hr
1,100 m3/hr
13.5 A
18.5 A
230 V
1,430 r.p.m.
High
1,220 r.p.m.
Medium
1,020 r.p.m.
Low
Quiet
860 r.p.m.
1,480 r.p.m.
High
1,220 r.p.m.
Medium
1,020 r.p.m.
Low
Quiet
860 r.p.m.
1,050 r.p.m.
1,100 r.p.m.
NOISE LEVEL
INDOOR UNIT
(Cool)
INDOOR UNIT
(Heat)
OUTDOOR UNIT (Cool)
OUTDOOR UNIT (Heat)
COMPRESSOR AND REFRIGERANT
TYPE
DISCRIMINATION
WEIGHT WITH OIL
PRECHARGED REFRIGERANT
REFRIGERANT TYPE
Pipe length
FULL CHARGE
ADDITIONAL CHARGE
MAXIMUM HEIGHT DIFFERENCE
DIMENSIONS
INDOOR UNIT
OUTDOOR UNIT
WEIGHT
INDOOR UNIT
Shipping / Net
OUTDOOR UNIT
Shipping / Net
1
High
47 dB
Medium
42 dB
Low
37 dB
Quiet
32 dB
High
48 dB
42 dB
Medium
37 dB
Low
Quiet
32 dB
53 dB
56 dB
Hermetic type,
4 pole, Rotary,
DC inverter motor
808-217-80(B)
10.2 kg
1,650 g
R410A
15 m
1,650 g
30 m
1,950 g
20 g/m
20 m
H x W x D
320 x 998 x 238 mm
H x W x D
578 x 790 x 315 mm
18 kg / 14 kg
47 kg / 43 kg

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aoyg24lfl

Table of Contents