Section 9. Trouble-Shooting Chart - Weil-McLain WM2AC13018 Installer's Information Manual

13 seer condensing unit
Hide thumbs Also See for WM2AC13018:
Table of Contents

Advertisement

SECTION 9. TROUBLE-SHOOTING CHART

WARNING: Disconnect all power to unit before servicing. Failure to shut off power can cause electrical shock resulting
in personal injury or death.
Symptom
Unit will not operate
Outdoor fan on;
Compressor off
Too little cooling
Compressor
operates
in
short cycles
High head pressure;
Low suction pressure
High head pressure;
Normal suction pressure
Low head pressure;
High suction pressure
Low suction pressure;
Compressor cool;
Ice on indoor coil
High suction pressure;
Or
fluctuating
head
and
suction pressures
Pulsing noise at expansion
device or liquid line
Registers sweat
Installer's Information Manual
Possible Cause
Power disconnected or loose connection
Blown fuse / breaker tripped
Thermostat out of calibration – set too high
Contactor defective
Transformer defective
High pressure control open (if provided)
Run or start capacitor defective
Start relay defective
Loose wire
Compressor stuck, grounded or open motor
winding, open internal overload
Low voltage condition
Improperly sized unit
Improper indoor airflow
Incorrect refrigerant charge
Air, non-condensibles or moisture in system
Incorrect voltage
Defective overload protector
Refrigerant undercharge
Restriction in liquid line, expansion device or filter
drier
Lack of sufficient indoor airflow
Dirty outdoor coil
Refrigerant overcharge
Outdoor fan not running
Air or non-condensibles in system
Expansion device stuck in open position
Defective compressor valves
Low indoor airflow
Operating below 65degF outdoors
Moisture in system
Excessive load
Defective compressor
TXV hunting
Air or non-condensibles in system
Air or non-condensibles in system
Low indoor airflow
Correction
Check voltage at contactor in condensing unit
Replace fuses / reset breaker
Reset
Check for 24VAC at contactor coil – replace if
open
Check wiring – replace transformer
Reset – see high pressure correction (high
pressure control opens at 450 psig)
Replace
Replace
Check for correct voltage at compressor –
check and tighten all connections
Wait at lease 2 hours for overload to reset; if
still open, replace the compressor
Add start kit components
Recalculate load
Check – should be approximately 400 CFM
per ton
Charge per procedure in installation manual
Recover refrigerant, evacuate and recharge,
replace filter drier
At compressor terminals, voltage must be +/-
10% of nameplate marking when unit is
operating
Replace – check for correct voltage
Add refrigerant
Remove or replace defective component
Clean/check filters, registers, or evaporator
coil that may cause a restriction.
Clean coil
Correct system charge
Repair or replace
Recover refrigerant, evacuate and recharge
Replace expansion device
Replace compressor
Increase speed of blower or reduce restriction
– replace air filter
Add low ambient kit
Recover refrigerant – evacuate and recharge
– replace filter drier
Recheck load calculation
Replace
Check TXV bulb clamp – check air distribution
on coil – replace TXV
Recover refrigerant, evacuate and recharge
Recover refrigerant, evacuate and recharge
Increase speed of blower or reduce restriction
– replace air filter
Page 9

Advertisement

Table of Contents
loading

Table of Contents