SETTING
Setting procedure
Zero-point
adjustment
Initial setting
Adjust
Set [Output
zero-point
operation],
[Output mode],
and [Unit]
If key-protect has been set, make be to release key-protect before
operating the keys.
9
Please refer to '
KEY-PROTECT FUNCTION' for the
procedure.
Zero-point adjustment
The displayed differential pressure when the pressure port is left
open is adjusted to zero.
Set to sensing mode
The sensor will automatically enter the
sensing mode when power is supplied.
The figure on the left shows the display when
the pressure unit is set to 'mmH
'kPa'.
Perform zero-point adjustment
Let the pressure ports (Hi-port and Lo-port)
be at atmospheric pressure (i.e., no applied
pressure condition), and press, simultane-
ously, the increment key (
decrement key (
released, zero-point adjustment is complet-
ed and the sensor returns to the sensing
mode.
When the unit of 'kPa' has been selected,
If pressure has been applied during
zero-point adjustment,
when the keys are pressed. Bring the
applied pressure to atmospheric pressure
(i.e., no applied pressure condition) and
carry out the zero-point adjustment once
again.
Initial setting
Pressure [Output operation], [Output mode], and [Unit] of the
comparative outputs are set.
Set to initial setting mode
In the sensing mode, press
pressing
Initial setting is displayed.
If sensor is being used for the first time,
is displayed.
Set initial conditions
The settable digit blinks.
The settable digit changes when
pressed.
Upper and lower
threshold value setting
Enter lower
threshold value
(M1), upper
threshold value (M2)
O'.
2
is displayed if the pressure unit is set to
) continuously.
is displayed and, when the fingers are
blinks once after the keys are released.
is displayed
MODE
key.
Measurement
Commence
measurement
on completion
of setting
3nd digit
[Output mode and output operation]
Hysteresis mode ( ) (M1 < M2)
Comparative
) and
output
(NO setting)
Comparative
output
(NC setting)
Window comparator mode ( ) (M1 < M2)
Comparative
output
(NO setting)
Comparative
output
(NC setting)
key while
When operating in window comparator mode (
value (M1) and upper threshold value (M2) should be set with a
difference of 3 digits (0.03 kPa.D {3 mmH
key is
Change the setting of each digit as desired.
The setting is changed when
pressed.
Change with
key.
2nd digit
1st digit
Output operation
: Normally open (NO)
: Normally closed (NC)
Output mode
: Hysteresis mode
: Window comparator mode
Unit
: mmH
O
2
: kPa
Hysteresis
Lower threshold
Upper threshold
value (M1)
value (M2)
Hysteresis
Hysteresis
1 digit
1 digit
Lower threshold
Upper threshold
value (M1)
value (M2)
Set to sensing mode
Press
key.
MODE
Your set data is registered and the sensor
enters into the sensing mode.
Since the initial conditions which have been
set are stored in an EEPROM, they are not
erased even if the power supply is switched
off.
The figure on the left shows the display when
the pressure unit is set to 'mmH
key is
High pressure level
1 digit = 0.01 kPa.D
{1 mmH
O.D}
2
High pressure level
) lower threshold
O.D}) or more.
2
O'.
2