Lennox G50UHi Unit Information page 10

Hide thumbs Also See for G50UHi:
Table of Contents

Advertisement

b−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off
time (time that the blower operates after the heat demand
has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
unit is shipped with a factory fan off setting of 90 seconds.
Fan off time will affect comfort and is adjustable to satisfy
individual applications. For customized comfort, monitor
the supply air temperature once the heat demand is satis-
fied. Note the supply air temperature at the instant the
blower is de−energized. Adjust the fan−off delay to achieve
The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 4.
LED #1
97L48 − DIAG 1 Green
97L48 − DIAG2 Green
69M15 − DS1 Red
69M15 − DS2 Green
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS
FAST FLASH
SLOW FLASH
OFF
ALTERNATING
SLOW FLASH
SLOW FLASH
ON
ON
ON
OFF
FAST FLASH
SLOW FLASH
ALTERNATING
FAST FLASH
NOTE − Slow flash rate equals 1 Hz (one flash per second). Fast flash rate equals 3 Hz (three flashes per second).
É É
É É É É
ON
OFF
É É É É É É É É É É É É É É É É É É É É É É É É
DEMAND
É É É É É É É É É É É É É É É É É É É É É É É É É É
É É É É É É É É É É É É É É É É É É É É É É É É
CAI
IGNITOR
GAS VALVE
INDOOR BLOWER
*Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on OFF TIME" Setting.
TABLE 4
DIAGNOSTIC CODES
Make sure to Identify LED'S Correctly..
LED #2
SIMULTANEOUS
Power on − Normal operation.
SLOW FLASH
Also signaled during cooling and continuous fan.
SIMULTANEOUS
Normal operation − signaled when heating demand initiated at thermostat.
FAST FLASH
Primary or secondary limit switch open. Limit must close within 3 minutes or unit goes into 1
ON
hour Watchgurad.
Prove switch open
OR: Blocked inlet/exhaust vent;
SLOW FLASH
OR: Prove switch closed prior to activation of combustion air inducer.
ALTERNATING
Watchguard −− burners failed to ignite.
SLOW FLASH
OFF
Flame sensed without gas valve energized.
SLOW FLASH
Rollout switch open. OR: Low voltage pin connector improperly attached.
ON
OFF
Circuit board failure or control wired incorrectly.
ON
SLOW FLASH
Main power polarity reversed. Switch line and neutral.
FAST FLASH
Low flame signal. See table 17 for flame signal Replace flame sense rod.
The following conditions are sensed during the ignitor warm−up period only:
1) Improper main ground;
ALTERNATING
2) Broken ignitor; OR: Open ignitor circuit;
FAST FLASH
3) Line voltage below 75 volts.
(If voltage lower than 75 volts prior to ignitor warm-up, control will signal waiting on call from
thermostat, and will not respond.
SureLight Control Ignition Sequence Board
15 Sec.
20 sec.
Pre −Purge
Ignitor Warmup
É É É É É É É É É É
É É É É É É É É É É
a supply air temperature between 90° − 110° at the instant
the blower is de−energized. (Longer delay times allow for
lower air temperature, shorter delay times allow for higher
air temperature). See figure 7.
FAN-OFF TIME ADJUSTMENT
60sec.
OFF
ON
OFF
(Black square indicates switch position)
To adjust fan−off timing, flip dip switch to desired setting.
DESCRIPTION
y
4 Sec.Trial
Blower On"
for Ignition
Delay
É É É É É É É É É É É É É
É É É É É É É É É É É É É
FIGURE 8
Page 10
120sec.
90sec.
180sec.
ON
OFF
ON
OFF
FIGURE 7
End of
5 SEC
Heat Demand
Post
Purge
É É É É É É É É É É
ON
Blower
Off
Time