T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Mode Number
(Press i key
to change)
Select
Output stages
08
of cooling.
Cooling cycle rate. 09
10
Not used.
11
Changeover
12
(T7100F only).
Not used.
13
Degree tempera-
14
ture display.
Displaying
15
temperature.
Not used.
16 - 18
Extended fan
19
operation in
b
heating
.
Extended fan
20
operation in
cooling.
Fan key
21
adjustment.
Remote sensing.
22
Temperature
23
averaging
c
network
.
Not used.
24
Keypad lockout
25
level.
Not used.
26
Heating/cooling
27
override.
Not used.
28 - 29
Deadband.
30
Interstage control
31
point (select
models).
Minimum On time. 32
Minimum Off time
33
for the
compressor.
b
Mode 01 or 02 must be 01 to extend fan operation.
c
Mode 22 must be set to 01 and remote sensor(s) must be installed.
69-0964–2
Table 2. Thermostat Installer Setup Options (Continued).
Factory-Setting
Display
Description
02
Two stages of cool.
04
Stage 1.
04
Stage 2.
00
System setting key is
operational.
00
Temperature is
displayed in °F.
00
Temperature is
displayed.
00
No extended fan
operation after the call
for heat ends.
00
No extended fan
operation after the call
for cool ends.
00
Fan setting key is
operational.
00
Remote sensing not
activated.
00
Temperature averaging
disabled.
0
No lockout.
00
No temperature change
when override key is
pressed.
02
Heating and cooling
setpoints can be set no
closer than 2°F.
01
Temperature has to
(Conven-
change 1°F or 2°F
tional) or
before the system calls
02 (Heat
for the next stage.
pump).
02
2-minute minimum On
time for heating and
cooling.
04
4-minute minimum Off
time for the compressor.
(Press
Display
00 or 01 00—No cooling.
03
01 or 02 01—Manual changeover
01
01
01
01
01
01
01
01 - 02
01 - 15
03 - 10
00 - 12
00 or 01 No minimum On time or 1 minute
00, 01,
02, 03 or
05
4
Other Choices
or
key to change)
Description
01—One stage of cool.
3 cph.
02—Auto only.
Temperature is displayed in °C.
Temperature is not displayed.
Fan operation is extended
90 seconds after the call for
heat ends.
Fan operation is extended
90 seconds after the call for
cool ends.
Fan setting key is continuously in
the Auto position.
Remote sensing activated.
Temperature averaging between
local sensor and remote sensor(s)
activated.
01—View setpoint only.
02—Lockout all keys.
°F the temperature setting is
changed when the override key is
pressed. Temporary is displayed.
Heating and cooling setpoints can
be set no closer than the chosen
value.
Temperature has to change the
chosen value before the system
calls for the next stage.
minimum On time for heating and
cooling.
Minimum number of minutes (0
thru 5) the compressor will be off
between calls for the compressor.
(continued)