Electrical Installation; Power Connections - Intec SM-501 Series Installation And Maintenance Instructions Manual

Duct smoke detectors

Advertisement

SM-501 – Installation
Specifications subject to change without notice. | INST APD0191 D140113 | USA 150303 | Page 4 of 7

POWER CONNECTIONS

Prior to connecting input power to the duct unit, determine the correct input voltage/ current availability and ensure it is connected to the correct
terminals.
24VAC/VDC INPUTS
Terminals 5, 6
24VAC
50/60 Hz
0.2A MAX.
24VAC OPERATION
POWER
CONNECTIONS
CONNECTIONS
1
2
3
SM-501 DUCT SMOKE DETECTOR
FIREX DUCT SMOKE DETECTOR
WIRING
!
CAUTION: For terminals 7-15 do not use looped wire under terminals. Break wire run to provide for proper supervision of connections.
With detector head removed, connect one of the appropriate dedicated power sources to the applicable terminals (see above). Replace detector head and
the unit will be energized. The green pilot LED will be illuminated, and when pressing the test/reset button, the red alarm LED will be illuminated. This test
confirms the correct basic operation of the duct smoke unit, excluding the detector head (see functional testing).
In the event of a fire alarm, certain equipment may be required to be shut down. For example, shut down may be achieved by interrupting the fan supply
source to that particular piece of equipment when wired as indicated below.
EXAMPLE:
AC/+ /H
DEDICATED INPUT VOLTAGE
AC/- /N
1
150303
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols

ELECTRICAL INSTALLATION

24VDC
0.1A MAX.
+
-
24VDC OPERATION
SEE
ALARM
SEE
ALARM
CONTACTS
POWER
CONTACTS
10A
12 A
4
5
6
7
8
9
5
6
or
2
3
115VAC INPUT
Terminals 1,2,3.
115VAC 50/60 Hz
0.1A MAX.
115VAC OPERATION
ALARM
*TROUBLE
*TROUBLE
ALARM
CONTACTS
CON-
CONTACTS
CONTACTS
TACTS 10A
10A
10-A
12 A
10 11
12
13
14
15
*TROUBLE CONTACTS ARE SHOWN
*TROUBLE CONTACTS ARE SHOWN IN
IN NON-ENERGIZED CONDITION.
NON-ENERGIZED CONDITION. UNDER
UNDER NORMAL OPERATION
NORMAL OPERATION CONTACTS
WILL BE REVERSED.
CONTACTS WILL BE REVERSED.
FAN SUPPLY SOURCE
24VAC/VDC
115VAC
230VAC INPUT
Terminals 1,2,4.
230VAC 50/60 Hz
0.1A MAX.
G
H 1
230VAC OPERATION
REMOTE
REMOTE
ACCESSORIES
ACCESSORIES
16
17 18
19 20 21
7
8
9
In alarm 7 and 8 will
open, interrupting
voltage supply to fan
NC
C
NO
ALARM RELAY
H 2
4 of 6