Servicing Precautions - LG GC-B379S*QA Service Manual

Table of Contents

Advertisement

FEATURES OF REFRIGERANT (R600a)
• Achromatic and odor less gas.
• Flammable gas and the ignition (explosion) at 494°C.
• Upper/lower explosion limit: 1.8%~8.4%/Vol. Features of the R600a
refrigerator
• Charging of 60% refrigerant compared with a R134a model
• The suction pressure is below 1bar (abs) during the operation.
• Because of its low suction pressure, the external air may flow in the
cycle system when the refrigerant leak, and it causes malfunction in
the compressor.
• The displacement of compressor using R600a must be at least 1.7
times larger than that of R134a.
• Any type of dryer is applicable (XH-5, 7, 9).
• The EVAPORATOR or any other cycle part that has welding joint is
hidden in the foam. (If not hidden inside, the whole electric parts
must be tested with the LEAKAGE TEST according to the
IEC Standard.)
• The compressor has label of the refrigerant R600a.
• Only the SVC man must have an access to the system.
INSTALLATION PLACE
• Must be well ventilated.
• Must be 20 m3 or larger.
• Must be no-smoking area.
• No ignitable factors must be present.
UTILITIES
• Refrigerant cylinder (MAX NET 300g)
• Manometer
• Vacuum pump (600^/min)
• Piercing Clamp
• Quick coupler
• Hoses (5m-1EA, 1m-3EA)
• LOKRING
• Portable Leakage detector (3g/yearl)
• Nitrogen cylinder (for leakage test)
• Concentration gauge
MAKE SURE BEFORE SERVICING
• Refrigerant
Confirm the refrigerant by checking Name Plate and the label on the
compressor, after opening the COVER ASSEMBLY, BACK-M/C.
• If the refrigerant is R600a, you must not weld or apply a heat
source.
AIR RECHARGING IN COMPRESSOR
Before refilling the refrigerant, you must perform the test
according to Chapter 5 (TROUBLESHOOTING CHART).
When the defects are found, you must discharge the residual
refrigerant (R600a) in the outdoor. For discharging the refrigerant
R600a, break the narrow portion of tube extension by hand or with a
pipe cutter as shown in Figure 1. Leave it for 3O min in outside to
stabilize the pressure with ambient. Then, check the pressure by
piercing the dryer part with piercing pliers. If the refrigerant is not
completely discharged, let the refrigerator alone for more 3O min in
outside.
POINT TO BE
BROKET
SERVICE TUBE
EXTENSION
Figure 1
Attach the service tube installed with a Schrader valve (one-way
valve) by using the LOKRING (Figure 2). Then, connect the Schrader
valve (one-way valve) to the pump that is connected to the
discharging hose leading to the outside. When discharging the
residual refrigerant, repeat 3 cycles that includes 3min of the pump
running
pump off
30 sec of the compressor running.
CHARGE TUBE
EXTENSION
SCHRADER VALVE
(ONE-WAY VALVE)
LOKRING
Figure 2
Figure 3
After the refrigerant (R600a) is completely discharged, repair any
defective parts and replace the dryer. At any case you must use the
LOKRING for connecting or replacing any part in the cycle
(No Fire, No Welding). Connect the Schrader valve to pump with the
coupler. And then turn the pump on for vacuum state (Figure 3). Let
the pump run until the low-pressure gauge indicates the vacuum
(gauge pressure 0, absolute pressure -1atm or -760mmHg).
Recommended vacuum time is 30 min. Charge the N2 gas in order
to check for leakage from welding points and the LOKRING. If
leakages are found, repair the defects and repeat the vacuum
process.
Figure 4
After the system is completely vacuumed, fill it with the
refrigerant R600a up to what has been specified at your refrigerator
Name Plate. The amount of refrigerant (R600a) must be precisely
measured within the error of ±2g by an electron scale (Figure 4).
REFRIGERANT (R600a) COUPLE CHARGING HOSE If you use the
manifold connected with both the refrigerant (R600a) cylinder and
the vacuum pump simultaneously, make sure the pump valve is
closed (Figure 5).
Connect the charging hose (that is connected to the refrigerant
(R600a) cylinder) to the Schrader valve installed on the service tube.
Then, charge the refrigerant (R600a) by controlling the Throttle
valve. When you do so, do not fully open the Throttle valve because
it may make damage to the compressor. Gradually charge the
refrigerant (R600a) by changing open and close the Throttle Valve
(5g at each time). The charging hose must use a one-way valve to
prevent the refrigerant refluence. Close the Schrader valve cap after
the refrigerant (R600a) is completely recharged.
After you completely recharge the refrigerant (R600a), perform the
leakage test by using a portable leakage detector or soapy water.
Test the low pressure (suction) parts in compressor off time and
high pressure parts in compressor on time. If the leakages are found,
restart from the refrigerant (R600a) discharging process and repairs
defects of leaks.
After the leakage test, check the temperature of each parts of the
cycle. Check with hands if the CONDENSER and the case
(HOT-LINE pipe) that is contacted to the door gasket are warm.
Confirm that frost is uniform distributed on the surface of the
4
EVAPORATOR.

SERVICING PRECAUTIONS