Flue Exhaust Connections - termovana Stella Installation, Maintenance And User Manual

Wall-mounted type c sealed-chamber condensing boiler
Table of Contents

Advertisement

The appliance is fitted with a by-pass that guarantees water flow on the exchanger for all
boiler operations.
When carrying out the discharge of the safety valve, it must be connected to a
discharge siphon which can be sight checked in order to avoid injuring people,
animals or objects. The manufacturer shall not be held responsible for such
injuries.
Warning
The flue exhaust connections must not come into contact with or be near
flammable materials and must not go through building structures or walls
If a new Type C boiler is installed to replace an old one, the whole fume
Warning
Ensure that the discharge and ventilation passages are not obstructed.
This sealed chamber boiler must only be installed together with a flue
exhaust device supplied by the boiler manufacturer, as required by UNI
7129 and 7131 standards.
This kit is supplied separately and according to the different installation facilities. For
further information on inlet/ flue devices, refer to the Termovana list of accessories.
This Type C boiler has been designed to fit a coaxial flue inlet/ exhaust system (Ø 60 –
100) or a roof discharge, always coaxial, with an appropriate adapter (Ø 80 – 118).
*
*

Flue exhaust connections

made of flammable materials.
extraction and flue exhaust system must also be replaced.
Ensure that the flue exhaust connections do not leak.
For a "STELLA 24" model: 4 m long max + a 90º bend
For a "STELLA 28" model: 3 m long max. + a 90º bend