7a
Start-up — preparation
Inspect system water piping
After filling the boiler and system with water,
throughout the system for leaks. If found, repair immediately.
Repeat this inspection after the boiler has been started and the
system has heated up.
Leaks must be repaired at once.
do so can damage the boiler, resulting in
substantial property damage.
Do not use
sealing compounds
damage to boiler will occur, resulting in sub-
stantial property damage.
7b
Start-up — operate boiler
Final check before starting boiler
• Read manual Section
9
, including the
9c
(Section
).
• Verify the boiler and system are
• Verify the
Start-up preparation
been completed.
Start the boiler
• Follow the
Operating instructions
the boiler.
7c
• See Section
if boiler fails to start.
Check system and boiler
1.
Check system piping and domestic hot water piping for leaks.
If found, shut down boiler and repair immediately.
.
Vent air from system
using manual vents. Air in the system
will interfere with circulation and cause heat distribution
problems and noise.
3.
Inspect vent system
thoroughly for signs of deterioration
from corrosion, physical damage or sagging. In addition
— Check for gas-tight seal at every connection and seam.
4.
Check around the boiler
of Section
7a
of this manual.
5.
Verify operation
per Section
8
cedure in Section
, and fill in the
certificate
on the same page.
Part Number 550-110-290/0107
inspect all piping
Failure to
petroleum-based cleaning or
in boiler system. Severe
Operating instructions
full of water
.
procedures of Section
from Section
9c
for gas odor following the procedure
7b
. Perform check-out pro-
Installation and service
(continued)
Inspect base insulation
Check to make sure
the base. If insulation is damaged or displaced,
boiler. Replace or reposition insulation.
7a
have
to start
The boiler contains ceramic fiber and fiber-
glass materials. Use care when handling these
materials per instructions on
manual. Failure to comply could result in
severe personal injury.
insulation is secure
against all four sides of
Failure to replace
damaged insulation or
reposition insulation can result in a fire haz-
ard, causing severe personal injury, death or
substantial property damage.
Do not use
petroleum-based cleaning or
sealing compounds
in boiler system. Se-
vere damage to boiler will occur, resulting
in substantial property damage.
Eliminate all system leaks.
Continual fresh
makeup water will reduce boiler life. Min-
erals can build up in sections, reducing
heat transfer, overheating cast iron, and
causing section failure.
Glycol or antifreeze leaks around the boiler
may result in fire, causing severe personal
injury, death or substantial property dam-
age.
Venting system must be sealed gas-tight
to prevent flue gas spillage and carbon
monoxide emissions which will result in
severe personal injury or death.
If you discover evidence of any gas leak,
shut down the boiler at once. Find the
leak source with bubble test and repair
immediately. Do not start boiler again
until corrected. Failure to comply could
result in severe personal injury, death or
substantial property damage.
page 68
of this
do not
operate
31