Quick installation and operating manual KT-Elektronik Disclaimer of liability We are constantly developing our products and therefore, reserve the right to change the product or the information contained in this document at any time without notice. We do not assume any liability for the accuracy or completeness of these mounting and operating instructions. Moreover, we do not guarantee that the buyer can use the product for an intended purpose.
KT-Elektronik SOL3-5 The SOL3-5 is a controller for solar thermal systems, and includes at max. nine temperature sensor inputs, five switching outputs, one pulse input and one 0-10V input or output. The controller is ready to use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller.
Page 4
Quick installation and operating manual KT-Elektronik System T. 21 T. 23 T. 24 T. 26 T. 27 T. 29 T. 30 System T. 21 T. 23 T. 24 T. 26 T. 27 T. 29 T. 30 I - I.0.0 CP1 2 - 2.
KT-Elektronik SOL3-5 Systems The SOL3-5 provides 72 different hydraulic systems. These differs in basic system components and extentions. Basic system components Extentions number of collector arrays, heating circuit, • • number of storage tanks, auxilary heater, • • • switching between collector arrays and storage tanks using •...
Page 6
Quick installation and operating manual KT-Elektronik System I o 2.0.0 System 2 o 2.0.0 System 3 o 2.0.0 1 collector array, 2 storage tanks (valve), 2 collector arrays (valve), 2 collector arrays (2 pumps), external heat exchanger 2 storage tanks (valve), 2 storage tanks (valve), external heat exchanger external heat exchanger...
KT-Elektronik Display System scheme The controller SOL3-5 it equipped with a graphical display. The display allows it to visualize the current system scheme with all relevant sensor informations as welll as state informations of pumps and valves for a quick overview of the operating condition of the system.
KT-Elektronik SOL3-5 Information level At the normal rotary switch position ,„Information level“, the system scheme, time, date as well as relevant temperatures measured by the connected sensors and state informations of pumps and valves of the selected hydraulc schema. By turning and pushing the rotary pushbutton it is possible to show time, date, temperature, and query the values of connected sensors and their setpoints.
For systems that do not contain the functional groups mentioned, this chapter has no meaning, the display and input of times-of-use is not offered by the SOL3-5. Three times-of-use can be set for each day of the week. If only one time-of-use is required, start and stop of second time-of-use must be equal.
KT-Elektronik SOL3-5 Setting the system code number (selection of the hydraulic scheme) During the system choice the system scheme associated with the system code number is displayed graphically, so the choice is possible using the concrete image. The modification of the system code number resets the previously set function blocks to the factory setting (FS).
Quick installation and operating manual KT-Elektronik Turn rotary pushbutton: Select funktion to activate or deactivate function (1/0) Push rotary pushbutton: Confirm selection Function block 'F01 Forced pump op. 0' is shown Turn rotary pushbutton: Activate or deactivate function (1/0) Push rotary pushbutton: Confirm activation or deactivation of function; Function block parameter Some functions that can be configured via function blocks require additional parameters.
KT-Elektronik SOL3-5 Resetting to default values All parameters and function blocks set over the rotary switch as well as parameters in PA parameter levels and function blocks in CO configuration levels can be reset to their default settings (factory default).
KT-Elektronik SOL3-5 CO4: DHW heating Function Comment Thermal desinfection CO4 -> F14 - 1 only with CO4 -> F01 - 1 Function block parameters: Day of week / 1, 2, …, 7, 1–7 (3) Start time / 00:00 to 23:45 (00:00)Stop time / 00:00 to 23:45 (04:00) Desinfection temperature / 60 to 90 °C (70 °C)
Quick installation and operating manual KT-Elektronik Dial-up also upon corrected CO6 -> F06 - 1: 1: Dial-up to GLT also to indicate that an error has been corrected , error only with CO6 -> F03 - 1 Control system monitoring CO6 ->...
KT-Elektronik SOL3-5 Max. storage tank 2 temperature switch ON condition 50 to 160 °C 58°C PA3.06 Mode of storage tank priority 1 to 5 PA3.07 Min. storage tank temperature for charging 5 to 90°C 30°C PA3.08 Only in mode 2 of storage tank priority...
Page 18
Quick installation and operating manual KT-Elektronik Modem dialing pause (P) 0 to 255 min PA6.04 Modem time-out (T) 1 to 255 min PA6.05 Number of redialing attempts to building control station (C) 1 to 255 PA6.06 Phone number of control station (TELnr) Max.
Approx. 0,5 kg Material Mat.-Nr. Identification Despription 37386 SOL3-5 SOL3-5 Solar thermal and differential temperature controller 11982 USB-L3 USB-Communickation cable to connect SOL3 und WPR3 to USB (PC) 11988 KOM232PC Adapter to connect SOL3 and WPR3 to RS232 interface (PC)