Heat-N-Glo 8000TRD Installer's Manual page 13

Table of Contents

Advertisement

VENTING WITH ONE (1) 90° ELBOW
V
1' MIN. (305mm)
2' MIN. (610mm)
3' MIN. (914mm)
4' MIN. (1.22m)
V+H=40' MAX. (12.4m)
NOTE: On vertical venting configurations, where
the vertical component is over 10 feet, install
the flue restrictor included in the manual bag
assembly to improve flame appearance.
Figure 12. Venting with One 90° Elbow
VENTING WITH ONE (1) 90° ELBOW
V (FT.)
1' MIN. (305mm)
2' MIN. (610mm)
3' MIN. (914mm)
4' MIN. (1.22m)
V+H= 40' MAX. (12.4MM) H = 20' MAX. (6.2m)
H
Figure 13. Venting with One 90° Elbow
H
2' MAX. (610mm)
4' MAX. (1.22m)
6' MAX. (1.86m)
8' MAX. (2.4m)
H = 8' MAX. (2.4m)
H (FT.)
5' MAX. (1.52m)
10' MAX. (3.1m)
15' MAX. (4.65m)
20' MAX. (6.2m)
V
NOTE: For corner installations: A 6-inch (152mm)
section of straight pipe may need to be attached to
the fireplace before a 90
pipe to clear the top standoffs.
NOTE: If a 90
the maximum horizontal run is 3-feet (914mm). (In
an LP unit the maximum horizontal run in this
situation is 30 inches (762mm).
V
H
o
elbow, to allow the vent
o
elbow is first attached to the unit,