Overview Of Further Operating Parameters Dhc; Overview Of Operating Parameters Dhc - Honeywell DHC 23 Operating Instructions Manual

Digital district heating controller
Table of Contents

Advertisement

DHC 23
Programming switch
Service switch
Push and turn knob
SERVICE BY THE HEATING SPECIALIST

Overview of operating parameters DHC 23-2

q
Turn programming switch into auto position..
w
Different values can be displayed by turning the service switch into the positions
0 ... F (see Table).
e
The parameters can then be changed with the aid of the push and turn knob.
Overview of operating parameters DHC 23-2
Position Operating parameter
0
Time
1
Day, month or year
2
Max. flow setpoint
3
Night setpoint
4
Frost protection limit
5
Heating characteristic slope
6
Building construction
for optimization
0 = optimization off
1 = light construction
2 = medium construction
3 = heavy construction
7
Valve actuator M1 running time
8
Valve actuator M2 running time
9
Max. inlet temperature in *
WW heat exchanger (VF
A = 10
District heating valve minimum lift
B = 11
Maximum district heating return
temperature in heating mode
C = 12
Onset point of floating district
heating return temperature limitation
D = 13
Reset time
E = 14
Controller gain
F = 15
(not used)
* Only for layered domestic hot water storage tank operation
Range
0:00...23:59
1990...2089
30 ... 120°C
0...20°C
-10... 1 5°C
0.4...4.5
0, 1, 2, 3
10... 1 800 s
10... 1 800 s
40...90°C
)
1
0...30 %
40...90°C
-20... 1 0°C
1...30 min.
}
M 1
1...30%/K
Basic setting
current time
current date
90°C
10°C
2°C
1.6
0
120 s
30 s
90°C
0 %
90°C
10°C
3 min.
3 %/K
19