Haier YR-H 71 Service Manual page 39

Controller and accessory for air conditioner
Hide thumbs Also See for YR-H 71:

Advertisement

43
Master discharge temp. sensor alarm in
low frequence
44
Communication error between master
unit MB89F538 and MCU 807(indoor)
Communication error between master
45
unit MB89F538 and MCU 807 (indoor)
MB89F538 and 807 central controller
Communication error between master
46
unit connecting board and inverter PCB
49
Master inverter drive PCB EEPROM
error
50
The total capacity of indoor units is too
high
51
Outdoor communication signal is lost
52
Indoor units is over than 64 sets
53
Central control address repeat
54
Master unit oil temp. is over-low
69
Slave unit is lost
70
Shortage of refrigeration
When inverter compressor frequence is lower than 30Hz,
TD1 is higher than 110
No signal for over 4 minutes
No signal from indoor unit or central controller for over 4
seconds
No signal for over 2 minutes
EEPROM data is lost or installed in wrong way.
Total capacity of indoor units>outdoor capacity x 135%
Check the address of all indoor units
In running, the temp. of compressor oil is lower than
(ps+10
for 5 minutes
Communication of slave unit error or switched off
Only show diagnostic code, doesn t stop units