Ventilation Information - Worcester Greenstar Utility 32/50 User Instructions & Customer Care Manual

Floor standing oil-fired condensing boiler conventional flue & room sealed flue
Hide thumbs Also See for Greenstar Utility 32/50:
Table of Contents

Advertisement

8 716 109 712b 07.10
Conventional flue boilers require an adequate supply of fresh air which must be delivered to the boiler
for combustion purposes through a permanent inlet, such as an air brick, into the area where the
boiler is situated.
If a cupboard or compartment which is to be used for storage or airing is built around the boiler after
installation there must be a non-combustible partition around the boiler. Further information can be
found in BS 5410 which also describes venting requirements.
Conventional flued boilers:
Minimum area of of air inlet for combustion:
2
248cm
for 32/50kW appliances.
MINIMUM AIR VENT AREA (cm
1 Internal air to and from a space/room inside the building. 2 External air to and from directly outside the building.
Conventional flue
1
Internal
ventilation External
High
kW
Level
32/50
495
50/70
715
Venting compartments:
Ventilation must be provided for boilers fitted into compartments as described in BS 5410
A minimum of two air vents must be fitted, one at low level and another at high level onto the
same wall using the same air for circulation.
Combustion air must not be taken from a room or internal space containing a bath or shower and
must not communicate with a protected area such as a hall, stairway, landing, corridor, lobby,
shaft etc.
Air vents must allow access for clean free air and must be sited to comply with the flue
terminal position requirements.
Air ducting runs must not exceed 3m.
Low level air vents must be less than 450mm from the floor.
A warning label must be attached to the vents with a statement to the effect:
''Do not block this vent.
Do not use for storage''.
12/7/10
12:28
Page 13
2
358cm
for 50/70kW appliances.
) FOR BOILERS INSTALLED IN A COMPARTMENT:
2
2
ventilation
Low
High
Low
Level
Level
Level
743
248
495
1073
358
715
GREENSTAR UTILITY 32/50 - 50/70
8 716 109 712b (07.2010)

VENTILATION INFORMATION

Room Sealed flue:
1
Internal
ventilation External
High
Low
kW
Level
Level
32/50
495
495
50/70
715
715
VENTILATION INFORMATION
2
ventilation
High
Low
Level
Level
248
248
358
358