Download Print this page

Installation Instructions; How To Order - Murphy TSB Specification Sheet

Murphy direct mount temperature switch specification sheet

Advertisement

Dimensions
2-1/4 in.
(57 mm)
NO C NC
Slot head terminal
screws (4-40, UNC-2A)

How to Order

To order the TSB model use the diagram below.
TSB
R230
Standard Switch Trip Point
Specify trip point value. Example: TSB-R200
Standard Switch Trip Point
Values (rising)*
R165 = 165°F (74°C)
R180 = 180°F (82°C)
165– 210°F ±5°F (±2.7°C)
R200 = 200°F (93°C)
Water/glycol 10% used for
R205 = 205°F (96°C)
setpoint
R210 = 210°F (99°C)
R220 = 220°F (104°C)
215– 230°F ±7°F (±3.8°C)
R225 = 225°F (107°C)
240– 250°F ±10°F (±6.5°C)
R230 = 230°F (110°C)
Heat transfer fluid used for
R240 = 240°F (116°C)
setpoint (276 viscosity @ 100°F)
R250 = 250°F (121°C)
*
Non standard trip points require a minimum quantity order.
Trip point must be in 5°F increments between 165– 250°F (74–121°C).
Switch Reset Differential
±15°F (±8.3°C)
Switch Repeatability
±3°F (1.7°C)
Connection Size
**
Blank = 1/2-14 NPT
10-05-0131
1/4 = 1/4-18 NPT
10-05-0167
3/8 = 3/8-18 NPT
10-05-0069
5/8 = 5/8-18 UNF
10-05-0068
3/4 = 3/4-14 NPT
10-05-0105
7/8 = 7/8-9 UNC
10-05-0093
3/8B = 3/8-19 BSPT
10-05-0284
1/2B = 1/2 BSPT
10-05-0330
M14 = 14 mm x 1.5
10-05-0104
M16 = 16 mm x 1.5
10-05-0514
M18 = 18 mm x 1.5
10-05-0399
M20 = 20 mm x 1.5
10-05-0670
M22 = 22 mm x 1.5
10-05-0606
M24 = 24 mm x 1.5
10-05-0907
** Standard connection.
Includes copper seal.
www.fwmurphy.com
918.317.4100 Email: sales@fwmurphy.com
4-11/64 in.
2-1/32 in.
Diameter
(106 mm)
(52 mm)
5/8-18 UNF-2A
1/4 in. Dia.
(6 mm)
1-9/32 in.
1/2-14 NPT
(33 mm)
(standard)
3/8
Accuracy
**
In order to consistently bring you the highest quality, full featured products, we reserve the right to change
our specifications and designs at any time. MURPHY, the Murphy logo are registered and/or common law
trademarks of Murphy Industries, Inc. This document, including textual matter and illustrations, is copyright
protected by Murphy Industries, Inc., with all rights reserved. (c) 2006 Murphy Industries, Inc.
TSB-9137B page 2 of 2

Installation Instructions

Mounting
1. The TSB can be mounted in horizontal or vertical angles (do not
mount the switch facing down).
2. Install the TSB switch in the engine water jacket location
recommended by the engine manufacturer.
3. Install the appropriate adapter nut into the engine water jacket. Use
thread sealant such as Teflon
4. Insert the sensing bulb through the adapter nut. The sensing bulb
must be fully immersed in coolant/liquid flow so liquid flows
across the sensing bulb.
5. Tighten the 5/8-18 UNF-2A compression nut to complete a liquid
tight seal.
Wiring
CAUTION: DISCONNECT Electrical
Power before wiring.
1. See wiring schematic below.
Switch contacts are shown with no
temperature applied to the
TSB switch.
2. A spade (forked) terminal
is recommended for all TSB
switch connections.
3. Complete the wiring operation
making sure the voltage and current requirements are within the
TSB switch electrical rating.
Teflon is a trademark of Dupont.
Warranty
A limited warranty on materials and workmanship is given with this FW
Murphy product. A copy of the warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm
WRONG
UP
®
tape as necessary.
Normally
Closed (N.C.)
Common (C)
Normally
Open (N.O.)
10 91 181
Printed in U.S.A.