Connecting electric dryers (cont.)
USA only
WArNiNg
w
• Connect the power cord to the terminal block. Connect
each power cord wire to the terminal block screw that has
the same colored wire. For example, connect the black
power cord wire to the terminal block screw with the black
wire. Failure to follow these instructions may result in a
short, overload, fire or death.
• Grounding through the neutral conductor is prohibited
for: (1) new branch-circuit installations, (2) mobile homes,
(3) recreational vehicles, and (4) areas where local codes
prohibit grounding through the neutral conductor.
four-wire connection for electric dryers: direct wire
• A 4-wire connection is required for all mobile and manufactured
home installations, as well as all new construction after January 1,
1996.
• A UL-listed strain relief is required.
1. Remove 5 inches (12.7 cm) of the outer covering from the wire.
Remove 5 inches of insulation from the ground wire. Cut off
1
approximately 1
⁄₂ inches (3.8 cm) from the other three wires
and strip 1 inch (2.5 cm) insulation from each wire. Bend the
ends of the three shorter wires into a hook shape.
(12.7 cm)
2. Remove the terminal block access cover on the upper back of
the dryer. Install a UL-listed strain relief into the power cord
through-hole; then thread the power cable prepared in Step 1
through the strain relief.
UL-Listed
4-Wire Power
Cord
1" (2.5 cm)
Ground Wire
5"
Terminal
Block
UL-Listed
Strain Relief
iNSTALLATiON iNSTruCTiONS
• Use UL-listed 4-wire #10 AWG-minimum copper conductor
cable.
• Allow at least 5 ft. (1.5 m) length to allow for removal and
reinstallation of the dryer.
3. Transfer the dryer's ground wire from behind the green ground
screw to the center screw of the terminal block. Attach the two
hot leads of the power cable to the outer terminal block screws.
Attach the white neutral wire to the center terminal block
screw. Attach the power cable ground wire to the green ground
screw. TIGHTEN ALL SCREWS SECURELY. Reinstall the terminal
block access cover.
Hot
(Black)
Ground
Screw
Power Cord
Ground Wire
25
Neutral
(White)
Hot
(Red)
White Wire
moved from
Ground Screw