WlM3 underfloor Heating Controller Wiring diagram WLM3-FS Continuously PE only COOLING SWITCH B1 B2 C1 C2 WLOC3 Top PCB String Unit number number To control X-OUTPUT (X-relay) DIP-5 DIP-6 DIP-7 (1-F) (1-9) for: ON / OFF Control WLM2 Compatible Boiler pump...
Description The WLM3 underfloor heating controller is suitable for connecting multiple room controllers/sensors and electric actuators (thermoheads) for an underfloor or radiator-based heating system. only oJ room controllers/sensors type Wlxx3 that are prepared for 2 wire or wireless communication can be used. For information on previous generations, see “special Features - replacing old masters”.
Attach the WLM3 master to a suitable wall. It will generally be convenient if the unit is situated within 0.8 m of the manifold, as most thermal actuators are supplied with 1 m cable. Cables can be run across the surface to the terminals using either the cable releases in the cover or by pressing out the cable entries in the lower part of the cover.
Delay times: Secondary UHF pump 180 sec. X-OUTPUT (configured as main pump) 190 sec. Free relay function (X-outPut) All WLM3 masters have a relay which can be to control X-outPut for: DiP-5 DiP-6 DiP-7 Fig. 6a utilized for a number of different purposes.
The voltage of the thermal actuators, 230V or 24V, must correspond that of the master. WLM3-xBA masters are for 230V thermal actuators, while WLM3-xFSmasters/add-on modules are for 24V thermal actuators. Up to 8 different zones can be controlled by the master. Connect the thermal actuator(s) on the loop(s) for each zone to the corresponding terminals on the master.
(i.e. its channel number) can be set with a screwdriver (see fig. 10). Up to 14 channels can be set on the selector, and there are two auxiliary channels (see later). A WLM3 master has 8 outputs. It can be connected with an add-on slave module with an additional 6 outputs, creating a system with 14 individual zones.
- wireless setup Fig. 11a WLxx3-29 wireless room sensors/controllers must be paired with a WLM3 master for wireless communication. To achieve this: 1. On the master, switch on DIP-3 to activate learning mode. 2. Initialize all wireless room controllers/sensors:...
Fig. 12a This feature, which limits supply water temperature, is available on full system masters, WLM3-xFS. The supply water sensor should be connected directly to the master via the terminals marked Supply Sensor. A temperature sensor of type ETF-522 must be used.
Similarly, a WLRC3 wireless receiver is connected to a WLM3 master using the plug-in connector provided with the receiver. For connecting a WLM3 master to another master in a network, a plug-in connector kit (WLM-NET) is available. CAT5 cable should always be used.
WLM3-BA/FS All masters must be interconnected using special cable via RJ14 socket 1 or 2. 4-port (For further information, see “Interconnection of WLM3 products”.) Network communication valve All masters must be connected in a daisy chain, NOT in a star formation (see WLM3-FS fig.
NOTE: For instructions on testing a network, see “Power-up recommendations”. using cooling functions WLAC 3 In addition to controlling heating, all WLM3 masters have the ability to control the cooling system. • T o enable the cooling function, a remote heating/cooling changeover module, WLAC3, and optional humidity sensor, WLHX3, must be connected.
• I f a dehumidifier is used, it can be connected via a relay using output 1 on the master and setting DIP-7 to “ON”. (NOTE: This output gives either 24V AC or 230V AC depending on the type of WLM3 master.
• T he next numerical output on the WLM3 master MUST be used for the secondary/boost function. • When the system is in cooling mode, 2-step control will be disabled. • The 2-step controller is available in wired or wireless version. NOTE: To avoid overloading the WLM3 master, we recommend that the secondary output is used as a signalling function for a remote relay.
Learn mode NOTE: This function conforms to BS/EN-1264 Part 4. Boiler test NOTE: Commissioning mode can only be activated on a WLM3-xFS master, and only if a supply water Install mode sensor is mounted. Otherwise, the function will be interrupted immediately.
When the masters acting as network slaves are in install mode (DIP-1 is ON), their power LED will flash briefly whenever communication is detected (approx. every 3 sec). The WLM3-xFS network master features a menu option that allows the number of network slaves present on the system, and whether there are any errors, to be checked.
Error number will be indicated by the number of flashes, with a pause of less than a 1/2 second between flashes. Indication will be followed by a pause of 2 seconds, after which the sequence will be repeated. Error codes can also be seen in the service menu of WLM3-FS masters (submenu 2).
CHANNEL F OPERATION (Channel 15) By fitting a WLTM3 sensor to a WLM3 system, and setting its hex encoder to Channel F, a single override function can be used to override all the automatic time and temperature functions of the master, including those areas independently controlled by a WLCT3 room controller.
Backward compatibility must be considered if an old master is replaced with a new WLM3 master. If any of the connected room sensors or room controllers are of the old type, DIP-9 (WLM2 Compatible) must be switched to ON.
10 seconds during that period, and the mixing valve, if fitted, will be opened and closed. Certifications CE marking OJ Electronics A/S hereby declares that the product conforms with the following Directives of the European Parliament and of the Council: Master...
Connect the AO module using the special cable included in the box. Connect a fused 230V AC mains supply. The sensor bus can be connected to either the WLM3 master or add-on module, using either bus (daisy chain) or star connections. Thermal actuators 1-8 are controlled by the WLM3 master while 9-14 are controlled by the add-on module.
Preset values are factory programmed but can easily be adjusted according to local needs via the display on the master. See the “Master with Display - Type WLM3” user manual for instructions on changing of the default factory settings. installation The unit should be mounted under the eaves of the roof or, alternatively, 2-3 metres above ground level.
Where a radiator circuit is used, it is possible to control room temperature using a special WLCT3 mode called Radiator Mode, thus optimizing energy savings. The controller measures the temperature in the room, and a zone valve is then controlled via the WLM3 master, which in turn activates the boiler on demand.
(i.e. its channel number) can be set with a screwdriver (see fig. 10). Up to 14 channels can be set on the selector, and there are two auxiliary channels with special functions. A WLM3 master has 8 outputs and additional slave modules, each with 6 outputs, can be connected creating a system of 14 individual zones.
The master is supplied with default temperature settings which are used by all room sensors connected to the system. With WLM3-xBA masters, the default DAY, NIGHT and OFF temperature settings are fixed (see “Factory Default Settings”) .
MIN. or MAX. temperature control. If set for MAX., the limit setting will be 27°C. If set for MIN., the limit setting will be 17°C. These temperatures are fixed when used with WLM3- xBA masters unless the room sensor has been allocated to a zone group controlled by a WLCT3 room controller.
Need help?
Do you have a question about the WLM3 and is the answer not in the manual?
Questions and answers
I want to know where I can buy this controller and the floor heating controller