NCPD / NCPE
Split-System Condensing Unit Installation Instructions
Before Installing Unit
1.
Check all local codes and ordinances that could affect in-
stallation. The manufacturer assumes no responsibility for
equipment installed in violation of any code requirements.
2.
Be sure that the electrical data specified on the unit rating
plate corresponds to what is available at the installation site
and NEC for installation requirements.
3.
Be sure that the electrical service provided to the building
can handle the load imposed by the unit.
4.
This unit should be installed in an outside wall for thru-the-
wall installation ONLY.
5.
NCP condensing units may only be used with indoor evapo-
rator coils utilizing an expansion (TXV) valve. Self-equaliz-
ing components are required to reduce compressor starting
problems. If self-equalizing components are not used, field
installed hard start kits will be required.
Hard start kits MUST be compatible with compressors.
Start Cap for Nominal Various Sizes
18,000 BTU (Bristol)
18,000 BTU (Copeland)
24,000 BTU (Bristol)
24,000 BTU (Copeland)
30,000 BTU (Bristol)
30,000 BTU (Copeland)
Start relays to be sized to µFd of capacitor used.
6.
The unit must be installed with the top level front to rear and
left to right.
Step 1 - Thru-the-Wall Installation
In thru-the-wall installation, due to the various types of wall
construction, it is not possible to provide detailed instructions.
The following is a list of general requirements and cautions for
installing these units.
1.
Masonry walls must have a lintel to support the wall.
2.
Extend the unit approximately 3/4" beyond outside surface
of the wall. Optional mounting angles can be purchased
from the factory or field fabricated for locating and mounting
the unit in the wall.
3.
The wall opening across the top and bottom must be
flashed. Bottom flashing to cover the full foot print of unit
and extend up 2'' on 3 sides. All openings around the top,
sides and bottom must be caulked and sealed. Care must
be taken not to plug the openings in the front of the base
pan of the unit.
THE UNIT MUST NEVER BE PLACED ON ITS SIDE OR UPSIDE DOWN AS THE COMPRESSOR OIL WILL RUN IN THE COOLING
CIRCUIT AND SERIOUSLY DAMAGE THE UNIT. BASE PAN MUST ALWAYS BE ON THE BOTTOM OF THE INSTALL.
National Comfort Products
µFd/Volts
145-175/330
88-106/330
145-175/330
88-106/330
145-175/330
88-106/330
1000 3000 4000 SERIES
If the optional wall sleeve is used, caulk the spaces between
the sleeve and the wall. Completely fill the clearance between
the unit and the wall sleeve with a polyurethane foam sealant
(Follow manufacturer's suggested application manual).
4.
During periods of rain and wind the primary drainage
path may not be adequate to handle the load. Secondary
precautions may also be required but not limited to the
following:
a. Seal flashing to unit
b. Floor drain
c. Additional field sealing of sheet metal joints
d. Sealing of unused access opening
5.
Clearances to air inlets and outlets must be adequate
to ensure no air flow obstructions or recirculation of
condenser air flow.
6.
Some architectural designs of buildings will require the unit
to be mounted behind a decorative grille. The performance
(capacity and efficiency) of the unit may be reduced with
the use of these decorative grilles.
The less resistive these grilles are to air flow, the better the units
performance will be.
Outdoor louvers provided by others must be approved by NCP
to maintain unit performance and warranty. Care must be taken
to locate coil intake side of unit away from loose debris that may
clog intake.
7.
If the unit is mounted behind a decorative grille, one or both
of the following items must be done to eliminate recircula-
tion of air to the unit:
a. The front of the unit must be mounted tight to the inside
of the architectural grille
b. A barrier must be provided to prevent recirculation of air
to the unit (mixing of inlet and outlet air) when the front
of the unit is mounted back from the inside of the arch-
tectural grille
8.
The unit must not be mounted in dead-end hallways or
areas where there is no fresh outside air circulation. Cool
fresh outside air must be provided for best unit operation.
Thru-the-wall units may not be located where hot exhausts
from clothes dryer vents, kitchen vents, steam vents or
corrosive fumes could come in contact with coil side of unit.
9.
30" clearance is required for service accessibility on the
inside. If more than one unit is to be installed in the same
area a min. of 48'' vertical must be maintained between
units to minimize recirculation of condenser exhaust air.
14299739 08/11/2014
1

Advertisement

Table of Contents
loading

Summary of Contents for National Comfort Product 1000 SERIES

  • Page 1 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 NCPD / NCPE 1000 3000 4000 SERIES Split-System Condensing Unit Installation Instructions If the optional wall sleeve is used, caulk the spaces between Before Installing Unit the sleeve and the wall.
  • Page 2: Step 3 - Leak Checking

    Step 2 - Installing Refrigerant Lines c. Braze the liquid line to the service valve. Allow the ni- trogen to keep flowing when brazing the refrigerant When replacing a R-22 system, it is recommended, that new line until all brazed joints are completed. Line Sets be used.
  • Page 3: Field Installation

    Figure 1 - Installing Refrigerant Lines Field Installation: Install the outdoor and indoor units per the manufacturer’s recommendations. Route the copper lines between the units. Step 1: Step 3: Step 5: The tubing should be cut Flux the copper tube and in- This is not a back seating square.
  • Page 4: Step 5 - Refrigerant Charging

    The system should be liquid-charged through the liquid-receiver Step 4 - Evacuation shut-off valve or through a valve in the liquid line. The use of a filter drier in the charging line is highly recommended. Because R410A Connect the vacuum pump to the service ports of the liquid and R407C are blends and scrolls have discharge check valves, line and the vapor line service valves.
  • Page 5: Sequence Of Operations

    When locating the room thermostat, it should be in the natural Sequence of Operations circulating path of room air. Avoid locations where the thermo- for Madison Avenue Option stat would be exposed to cold air infiltration; drafts from win- dows, doors or other openings leading to the outside; exposure to air currents from warm-or-cold air registers or to exposure The compressor crankcase heater will be energized as long as where the natural circulation of the air is cut off, such as behind...
  • Page 6 Wiring Schematic NCPD-XXX- 1010/D, NCPD-XXX-3010/D (Bristol Compressor)                                  ...
  • Page 7 Wiring Schematic NCPE-XXX-1010, NCPE-XXX-3010, NCPE-XXX-4010 (Copeland Compressor)                                  ...
  • Page 8 Wiring Schematic NCPE-XXX- 1010/D, NCPE-XXX-3010/D, NCPE-XXX-4010/D (Copeland Compressor)                                 ...
  • Page 9 Wiring Schematic NCPD-XXX- 1010/D, NCPD-XXX-3010/D (Bristol Compressor)                                  ...
  • Page 10 Wiring Schematic NCPD-XXX-4010, NCPDXXX-4010 (Bristol Compressor)                                   ...
  • Page 11 Wiring Schematic NCPE-XXX-4010 (Bristol Compressor)                                    ...
  • Page 12 Wiring Schematic NCPE-XXX-4010/D (Bristol Compressor)                                    ...
  • Page 13 SPECIFICATIONS CHART - 1000 SERIES MODEL NO. NCPD-418 NCPE-418 NCPD-424 NCPE-424 NCPE-430 DIMENSIONS 26 1/4” 26 1/4” 26 1/4” 26 1/2” 26 1/2” Service Width 28 5/8” 28 5/8” 28 5/8” 28 5/8” 28 5/8” Clearance Height 18 1/2” 18 1/2”...
  • Page 14 SPECIFICATIONS CHART - 3000 SERIES MODEL NO. NCPD-418 NCPE-418 NCPD-424 NCPE-424 NCPE-430 DIMENSIONS Service 24 1/8” 24 1/8” 24 1/8” 24 1/8” 24 1/8” Width Clearance... 32” 32” 32” 32” 32” Height 30” 18 1/2” 18 1/2” 18 1/2” 18 1/2” 18 1/2”...
  • Page 15 SPECIFICATIONS CHART - 4000 SERIES MODEL NO. NCPD-418 NCPE-418 NCPE-424 NCPE-430 Service DIMENSIONS Clearance. 30” 30” 30” 30” Width 30” 23” 23” 23” 23” Height 18 1/2” 22 1/2” 22 1/2” 22 1/2” Length 3/8” 3/8” 3/8” 3/8” Liquid Valve 3/4”...
  • Page 16: Replacement Parts Guide

    National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPD SERIES 1000 NCPD1000/D SERIES **ADDITIONAL PARTS - MADISON SERIES ONLY DESCRIPTION NCPD-418 NCPD-424 Contactor 14262082 14262082 ITEM DESCRIPTION 4000 SERIES Dual Run Capacitor...
  • Page 17 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPE SERIES 1000 NCPE1000/D SERIES New Photo to Come With Scroll Compressor With Scroll Compressor **ADDITIONAL PARTS - MADISON SERIES ONLY DESCRIPTION NCPE-418 NCPE-424...
  • Page 18 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPD 3000 SERIES NCPD 3000/D SERIES **ADDITIONAL PARTS - MADISON SERIES ONLY DESCRIPTION NCPD-418 NCPD-424 Contactor 14262082 14262082 ITEM DESCRIPTION 3000 SERIES...
  • Page 19 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPE 3000 SERIES NCPE 3000/D SERIES New Photo to Come With Scroll Compressor With Scroll Compressor ITEM DESCRIPTION NCPE-418 NCPE-424 NCPE-430...
  • Page 20 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPD 4000 SERIES NCPD 4000/D SERIES **ADDITIONAL PARTS - MADISON SERIES ONLY DESCRIPTION NCPD-418 Contactor 14262082 ITEM DESCRIPTION 4000 SERIES Dual Run Capacitor Time Relay on Make...
  • Page 21 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 REPLACEMENT PARTS GUIDE NCPE 4000 SERIES NCPE 4000/D SERIES New Photo to Come With Scroll Compressor With Scroll Compressor ITEM DESCRIPTION NCPE-418 NCPE-424 NCPE-424...
  • Page 23 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 LIMITED EXTENDED PROTECTION WARRANTY NATIONAL COMFORT PRODUCTS (NCP) BENSALEM, PA SPLIT-SYSTEM CONDENSING UNITS This NCP product is warranted to be free from all manufacturing defects, material or workmanship, for a period of one year from the date of installation (receipt required), whether or not actual use begins on this date, or one year from the date of manufacture if the date of installation cannot be verified.
  • Page 25 National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 PROCEDURE FOR WARRANTY FAILURE National Comfort Products are warranted for one year after the date of installation, or one year from the date of manufacture. The compressor carries an extended 5 year warranty after the date of installation.
  • Page 27: Engineering Specification Guide

    National Comfort Products 539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579 ENGINEERING SPECIFICATION GUIDE THRU-THE-WALL SPLIT SYSTEM CONDENSING UNIT SAFETY APPROVAL - Each unit shall be ETL listed for safety approval. GENERAL - Each outdoor condensing unit shall be factory assembled and run tested. THRU-THE-WALL APPLICATION - Each unit shall be designed for installation flexibility.
  • Page 28 NCPD/E Split-System Condensing Unit Installation Instructions - Rev 08/11/2014...

This manual is also suitable for:

3000 series4000 series

Table of Contents