12.1.7
Heat + Tank Mode Operation
Setting 1: When Heating priority is set by control panel:
1
3 ways valve control:
3 ways valve switch and fix to room side.
o
2
Heatpump operation control:
Heatpump operate follow normal operation
o
3
Backup Heater control:
Backup heater operate follow normal operation
o
4
Booster heater control:
Booster heater On/Off follow normal operation
o
5
Solar 3 way valve:
Solar 3 way valve operates follow solar operation specification.
o
6
2 ways valve control:
2 ways valve opens.
o
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF
Setting 2: When heating priority is not set by control panel:
When Solar Priority is set/not set by control panel:
1
3 ways valve control:
3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank
o
heat-up interval. Both mode will switch alternatively.
2
Heatpump operation control:
During heating heat-up interval
a.
Follow normal heating operation.
o
Under solar priority set condition:
-
Always detect the tank temperature after heating heat-up interval. Switch only to tank heat-up
interval and start counting tank heat-up timer when tank temperature < THERMO ON TEMP AND
solar 3WV OFF
Under solar priority not set condition:
-
Always detect the tank temperature after heating heat-up interval. Switch only to tank heat-up
interval and start counting tank heat-up timer when tank temperature < THERMO ON TEMP
* THERMO ON TEMP is defined form following Case1 to Case4.
During tank heat-up interval
b.
Heatpump tank target temperature = Tank set temperature or [55°C] whichever lower
o
Heatpump Water Outlet set temperature is set to Maximum (55°C) during tank interval
o
Case 1:
THERMO OFF TEMP:
o
THERMO OFF TEMP = Heatpump tank target temperature + [+2°C].
1.
Tank temperature > THERMO OFF TEMP for continuous 3 minutes, switch 3 ways valve to room side.
2.
End Tank heat-up interval and start count heating heat-up interval.
THERMO ON TEMP:
o
THERMO ON TEMP = Heatpump tank target temperature + [-3°C].
1.
After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval
2.
when tank temperature < THERMO ON TEMP.