Wall Sleeve Extension And Louver Frame - Remington IM 812-2 Installation & Maintenance Data

Packaged terminal air conditioners and heat pumps – c vintage
Table of Contents

Advertisement

The standard wall sleeve will accommodate the maximum wall
thickness described in Table 1, page 11. For thicker walls,
wall sleeve extensions are available from your local distribu-
tor. Air splitters will be included in the wall sleeve extension as
shown in Figure A.
Note: When installing a new chassis into an existing
wall sleeve with an extension, it will be necessary to
relocate the two air splitters to match the dimen-
sions shown in Figure A.
Installation
Wall sleeve extensions are shipped in a separate carton.
Install the wall sleeve extension as follows:
1.
Place a bead of caulk around the perimeter of the wall
sleeve and another bead around the mating side of the
wall sleeve extension so that the joint is watertight. Be
sure to use a resilient caulking, such as silicone.
2.
Assemble the wall sleeve extension to the wall sleeve
using fasteners by others. Make certain the caulking does
not block the weep holes.
3.
Attach indoor drain kit (if used) according to the instruc-
tions on page 7. Outdoor drain kits are not designed to
be used with sleeve extensions.
Louver Frame
Louver frames should be used for panel wall and thin wall
applications for positive anchoring to the wall. Recess the wall
sleeve so that the louver is flush with the outside of the build-
ing (if outdoor drain kits are being used, keep sleeve flush
with louver frame outer flange). Place louver frame around
sleeve as shown in Figure B. Drill holes and attach to sides
and top only.
!
CAUTION
Do not drill holes in the bottom of the wall sleeve as it
may cause leakage.
Anchoring
Anchor the wall sleeve in the opening as shown in Figure C.
IM 812 / Page 12 of 28

Wall Sleeve Extension and Louver Frame

Figure A. Wall Sleeve Extension
Wall
Sleeve
Extension
12"
24"
Air Splitters
Figure B. Louver Frame
Figure C. Anchoring Methods
Expansion
Molly or
Anchor
Toggle
Bolt
Bolt
Do Not Drill Holes
in Bottom of
Sleeve (Except for
Indoor Drain Kit)
Room
Side
42"
16"
6"
X
Wood
Screw
Cripple Stud
Main Stud

Advertisement