Vaillant ECOTEC PLUS VU 80 Installation And Maintenance Instructions Manual page 58

Table of Contents

Advertisement

14
Troubleshooting
Display
Meaning
D.033
Fan speed target value
D.034
Fan speed actual value
D.039
Solar feed temperature
D.040
Flow temperature
D.041
Return temperature
D.044
digitalised ionisation voltage
D.046
Pump type
D.047
Outside temperature
(with weather-controlled Vaillant controller)
D.050
Offset for minimum speed
D.051
Offset for maximum speed
D.060
Number of temperature limiter shutdowns
D.061
Number of ignition device cutoffs
D.064
Average ignition time
D.065
Maximum ignition time
D.067
Remaining burner anti-cycling time
D.068
Unsuccessful ignitions at 1st attempt
D.069
Unsuccessful ignitions at 2nd attempt
D.071
Target value maximum heating flow temperature
D.072
Internal pump overrun after
D.076
UNit variant (display)(device specific number)
D.077
Partial load for cylinder charging
D.080
Operating hours, heating
D.081
Operating hours, hot water generation
D.082
Number of burner start-ups in heating mode
D.083
Number of burner start-ups in hot water mode
D.084
Maintenance indicator: Number of hours until the next
maintenance
D.090
Status of digital controller
D.091
Status DCF with external sensor connected
D.093
DSN unit variant setting
D.094
Delete fault history
D.095
Software version eBUS components
D.096
Factory setting
13.2 Diagnostics codes at Installer level
(continued)
58
Display value/adjustable value
In rpm
In rpm
Actual value in °C
Actual value in °C
Actual value in °C
Display field 0 to 102,
> 80 no flame
< 40 good flame
0 = Relay with disable facility (default setting)
1 = PWM with disable facility
Actual value in °C
Adjustment range in rpm: 0 to 3000 (factory set nominal value)
Adjustment range in rpm: - 990 to 0 (factory set nominal value)
Number
Number of unsuccessful ignitions in the last attempt
In seconds
In seconds
In minutes
Number
Number
Adjustment range in °C: 40 to 85 (factory setting: 75)
Adjustment range in min: 0 to 10 (default setting: 2)
82 = VU GB 806/5-5
81 = VU GB 1006/5-5
80 = VU GB 1206/5-5
in kW
In hours (h)
In hours (h)
Number
Number
Adjustment range: 0 to 3010 h and "-" for deactivated
(Factory setting: "-")
1 = Recognised, 0 = Not recognised
0 = No reception, 1 = Reception, 2 = Synchronised, 3 = Valid
Adjustment range: 0 to 99
1 = Delete fault list
1. PCB
2. Display
4. VR34
1 = Reset all adjustable parameters to factory setting
ecoTEC plus installation and maintenance instructions 0020134823_01