TRUE ON LINE UPS 1. Introduction Contents This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. 1. Introduction The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current.
TRUE ON LINE UPS TRUE ON LINE UPS 2. Safety Instructions Installation for 6K / 10K PLEASE READ THE FOLLOWING USER MANUAL AND THE SAFETY INSTRUCTIONS Warning: This is a product for restricted sales distribution to informed partners. BEFORE INSTALLING THE UNIT AND STARTING IT UP! Installation restrictions or additional measures may be needed to prevent disturbances.
TRUE ON LINE UPS TRUE ON LINE UPS 3. Description of commonly used notations For 6K / 10K models, the maintain switch, bypass switch and input switch are still electrically live and dangerous even after the input switch and bypass switch are disconnected on carrying out servicing and/or maintenance.
TRUE ON LINE UPS TRUE ON LINE UPS 4. System Description Switch Function 3 Load/Battery Capacity LED 1. Turn on UPS system: 4 Load/Battery Capacity LED 2 Load/Battery Capacity LED By pressing the ON-Switch the UPS system is turned on. ON - Switch 5 Load/Battery Capacity LED 2.
Page 6
TRUE ON LINE UPS TRUE ON LINE UPS LCD display content and relative work model LCD Display Screen Main power in or first time UPS ON LCD display: Bypass LED Line LED WELCOME TO USE WELCOME TO USE Inverter LED O N L I N E O N L I N E U P S...
Page 7
TRUE ON LINE UPS TRUE ON LINE UPS Press the Display cycle button on front panel once more, LCD will display Press the Display cycle button on front panel once more, LCD will display as follows: as follows: INPUT FREQUENCY INPUT FREQUENCY LOAD CAPACITY LOAD CAPACITY...
Page 8
TRUE ON LINE UPS TRUE ON LINE UPS Communication Communication Input Switch Interface Interface Intelligent Slot Battery Connector(H Model) Battery Connector(H Model) Intelligent Slot Terminal Block Breaker 6KR Rear Panel Network/Fax/Modem Output Socket Surge Protection Communication Input Socket Interface Intelligent Slot 1KL Rear Panel Parallel Card Port(Option) Communication...
TRUE ON LINE UPS TRUE ON LINE UPS 5. Connection and Operation THE SYSTEM MAY BE INSTALLED AND WIRED ONLY BY QUALIFIED ELECTRICIANS IN ACCORDANCE WITH APPLICABLE SAFETY REGULATIONS! 5.1 Connection and operation for 1K / 2K / 3K WHEN INSTALLING THE ELECTRICAL WIRING, PLEASE NOTE THE 1KVAH External Battery Connection NOMINAL AMPERAGE OF YOUR INCOMING FEEDER.
Page 10
TRUE ON LINE UPS TRUE ON LINE UPS 2) Connection: 4-2) Without utility power connecting: 2-1) UPS Input Connection Even though utility power is connected to the UPS, the UPS still can be turned on by If the UPS is connected via the power cord, please use a proper socket with protection just simply pressing button continuously for more than 1 second.
Page 11
TRUE ON LINE UPS TRUE ON LINE UPS (2) One end of the external battery cord is a plug for connecting the UPS and the other end has 3 (or 2) open wires for connecting the battery pack. The battery connection procedure is very important.
TRUE ON LINE UPS TRUE ON LINE UPS 5) Battery Charge: Fully charge the batteries of the UPS system by leaving the UPS self-test, the UPS will get into bypass mode and the Utility Power LED and Bypass system connected to the mains for 8-10 hours. You can also use the UPS system LED will light up.
TRUE ON LINE UPS TRUE ON LINE UPS Please have the following information at hand before calling the After-Sales Service Remedy Problem Possible cause Department: No indication, no warning tone No input voltage Check building wiring socket outlet 1. Model number, serial number even though system is and input cable.
TRUE ON LINE UPS TRUE ON LINE UPS 8. Technical data 8.3 Typical stored energy time (Typical values at 25 minutes:) Model No. 100 % Load 50 % Load 8.1 Electrical specifications INPUT Model No. Voltage 115~300VAC 176~276VAC Frequency (46~54)Hz /(56~64)Hz Current(A) OUTPUT 8.4 Dimensions and weights...
TRUE ON LINE UPS TRUE ON LINE UPS 9. Communication port Harmonic Current: EN61000-3-2 Voltage Fluctuations and Flicker: EN61000-3-3 EMS: EN61000-4-2(ESD)............Level 4 9.1 RS232 Interface EN61000-4-3(RS) ..............Level 3 The following is the pin assignment and description of DB-9 connector. EN61000-4-4(EFT)..............Level 4 EN61000-4-5(lighting surge)...........Level 4 Description Pin #...
TRUE ON LINE UPS TRUE ON LINE UPS APPENDIX APPENDIX : Front panel LED display and Work Model parallelism diagram 6KVA and 10KVA: 1KVA, 2KVA and 3KVA: LED No LED No Alarm Work Model Work Model Alarm Beep Beep 0%~35% Load Capacity 0 ~35 Load Capacity 36%~55% Load Capacity 36 ~55 Load Capacity...
Page 17
TRUE ON LINE UPS TRUE ON LINE UPS APPENDIX : Parallel operation (6KVA and 10KVA) Input Switch Board 1. Brief introduction of the redundancy N+X is currently the most reliable power supply structure. N represents the minimum UPS number that the total load needs; X represents the redundant UPS number, i.e. The fault UPS number that the system can handle simultaneously.
Page 18
TRUE ON LINE UPS Parallel Installation Diagram I/P CHD I/P N I/P L I/P L I/P N I/P CHD...