How To Check Miswiring And Serial Signal Error - Mitsubishi Electric MSZ-GE09NA Service Manual

Split-type air conditioners
Hide thumbs Also See for MSZ-GE09NA:
Table of Contents

Advertisement

D How to check miswiring and serial signal error
MSZ-GE06/09/12/15/18NA
MSY-GE09/12/15/18NA
Is the bus-bar voltage of the inverter P.C. board or the outdoor electronic control P.C. board normal? (Refer
to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.
board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3
Turn OFF the power supply.
Remove the bridge between outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there rated voltage between indoor terminal block S1 and S2?
<Confi rmation of power voltage>
Is there amplitude of 10 to 20 VDC between indoor terminal block S2
and S3? <Confi rmation of serial signal>
A
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
• Reinstall
either the unit
or the light
away from
each other.
Is serial signal
• Attach a fi lter
error indicated 6
No
on remote
minutes later?
control receiv-
Yes
ing section
of the indoor
unit.
B
OBH548D
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
Turn ON the power supply.
Yes
Is there rated voltage between outdoor terminal block S1 and S2?
Press EMERGENCY OPERATION switch once.
Does the OPERATION INDICATOR lamp light
up? <Confi rmation of the power to the indoor
unit>
Yes
Is serial signal error indicated 6 minutes later?
Yes
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
B
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
S3. 1
Turn ON the power supply.
Yes
Yes
Yes
Yes
Is there 2 VDC or less between CN10A (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
Yes
Is there 2 VDC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Replace the indoor power
P.C. board and the indoor
terminal P.C. board
32
Check the power supply.
No
No
Is there any miswiring, poor
contact, or wire disconnec-
tion of the indoor/outdoor
No
connecting wire?
1. Miswiring may damage indoor electronic control P.C.
board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board or the outdoor electronic control P.C.
board is normal, LED blinks 6 times after 3 minutes.
(Except for outdoor unit of multi system type)
Replace the inverter P.C. board or the outdoor
electronic control P.C. board. 2
No
(Lighted
2. Be careful of the residual voltage of smoothing
or not
lighted)
Check the wiring
If there are any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
No
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
No
No
Is there 2 VDC or less between
CN10A (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
No
Yes
Replace the indoor elec-
tronic control P.C. board.
No
Check the wiring.
Correct them.
Yes
No
Check of power supply.
(Refer to the outdoor
No
service manual.)
capacitor.