n Hot-Start Control
• The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F).
• The operation diagram is as following.
Indoor unit
Heat-Exchanger
temperature
Hotstart Off
Hotstart On
Thermal
Outdoor fan
Indoor fan
4way Valve
• Initial Hotstart On state
¿ Power Off ‡ On
¡ Operation Off ‡ On
¬ Cooling operation ‡ Heating operation
√ Defrost operation
Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes
1 min
Setting fan
Off
Low
speed
1 min
ON
ON
Off
Low
ON
- 65 -
Operation Details
Setting fan
speed