Lynx Model LX-85
LYNX MODEL LX-85 NON-DIRECT VENT, SIDEWALL VENTING
All joints must be liquid and pressure tight. Use 3" dia. PVC/CPVC schedule 40 pipe or U/L listed single wall 3" dia.
AIR INTAKE
(DO NOT BL0CK)
Figure 7. Non-direct vent, side wall venting - utilizing PVC/CPVC pipe f or venting.
STANDARD
?
90
ELBOW
AIR INTAKE
(DO NOT BL0CK)
Figure 8. Non-direct vent, side wall venting - utilizing stainless steel vent materials f or venting.
** Definition of Snow Line: Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to.
The height should be used as the SNOW LINE.
* AL 29-4C IS A REGISTERED TRADEMARK OF ALLEGHENY LUDLUM CORP.
AL29-4C S.S.*. venting materials (See page 6).
SLOPE UP 1/4 IN.
PER FOOT MIN.
FROM BOILER TO
VENT TERMINATION
3 IN. DIA.
PVC/CVPC
PIPE FOR
VENT
˚
90
ELBOW
SLOPE UP 1/4 IN.
PER FOOT MIN.
FROM BOILER TO
VENT TERMINATION
3 INCH. DIA.
STAINLESS
STEEL VENTING
MATERIAL FOR
VENT
ADAPTOR
S/ F P / N 4 4 06 95 (ADJ US T ABL E
6" MIN.
9" MAX.
TERMINATION 90
WITH SCREEN
A U/L LISTED FLASHING
AND SEALING BOOT MUST
BE USED ON COMBUSTIBLE
WALLS.
OUTSIDE WALL
6" MIN.
9" MAX.
OUTSIDE VENT TERMINATION
ELBOW WITH SCREEN
A U/L LISTED WALL THIMBLE
MUST BE USED ON COMBUSTIBLE
WALLS. S/F P/N 440695
(ADJUSTABLE 5 IN. TO 8 IN.)
MAY BE USED. ABOVE THIMBLE
MUST BE USED WITH HEAT-FAB
SLIP JOINT CONNECTOR
OUTSIDE WALL
˚
ELBOW
12" MIN
SNOW LINE
(SEE DEFINITION)
12" MIN
SNOW LINE
(SEE DEFINITION)
9