BOILER START-UP

Elements
1 –LCD screen
2 – HUW signal icon
3 – HUW pump active icon
4 – HUW program active icon
5 – CH signal icon
6 – CH pump active icon
7 – CH program active icon
8 – current HUW temperature
9 – current CH temperature
10 – time
11 – data
12 – CH and HUW temperature setting icon
13 – floor heating icon
14 – room temperature icon (optional)
15 – weekday
16 – relays status
17 – function buttons
18 –ON/OFF + back button
19 – green diode – boiler turned on
20 – red diode – boiler turned off
21 – CHOOSE button
TECHNICAL DATA
Manual power
Power
distribution
4 kW
100% - 67% - 33%
4 kW
100% - 67% - 33%
6 kW
100% - 67% - 33%
6 kW
100% - 67% - 33%
9 kW
100% - 67% - 33%
9 kW
100% - 67% - 33%
12 kW
100% - 67% - 33%
15 kW
100% - 67% - 33%
18 kW
100% - 67% - 33%
21 kW
100% - 67% - 33%
24 kW
100% - 67% - 33%
AsB II boiler Manual power
(kW)
distribution
EKW 27
9 ÷ 18 ÷ 27
EKW 30
10 ÷20 ÷30
EKW 33
11 ÷22 ÷33
EKW 36
12 ÷ 24 ÷36
EKW 39
13 ÷ 26 ÷39
EKW 42
14 ÷ 28 ÷42
EKW 45
15 ÷ 30 ÷45
EKW 48
16 ÷ 32 ÷48
* Exact section should be matched by qualified electrician
** Exact heated area depends on multiple factors
2
8
10
11
12
18
Modulation of
Power
power
supply
by 1/3
1 phase
by 1/3
3 phases
by 1/3
1 phase
by 1/3
3 phases
by 1/6
1 phase
by 1/6
3 phases
by 1/6
3 phase
by 1/6
3 phases
by 1/6
3 phase
by 1/6
3 phases
by 1/6
3 phase
Power
Safety
Power cord
(V)
fuses (A)
(mm²)
400
3 x 50
5 x 16
400
3 x 50
5 x 16
400
3 x 50
5 x 16
400
3 x 63
5 x 16
400
3 x 63
5 x 16
400
3 x 80
5 x 25
400
3 x 80
5 x 25
400
3 x 80
5 x 25
3
4
1
5
6
c
11:53:33
12 05 2011 THU
ESC
ON
OFF
13
20
19
Safety fuses (A)
Power cord
(mm²)
1 x 20
3 x 2,5
3 x 6
5 x 1,5
1 x 32
3 x 10
5 x 2,5
1 x 40
3 x 10
3 x 16
5 x 2,5
3 x 20
3 x 25
3 x 32
3 x 40
3 x 40
5 x 10
Heated area
AsB II boiler Power
(m²)
220 - 380
EKW 54
240 – 400
EKW 60
260 – 450
EKW 66
280 – 480
EKW 72
290 – 500
EKW 96
300 – 520
EKW 120
320 – 570
340 – 600
EKW 144
9
7
1
2
3
c
4
5
6
17
Heated area
(m²)
~ 50
~ 50
3 x 4
~ 70
~ 70
~ 110
~ 110
5 x 4
~ 150
5 x 4
~ 180
5 x 6
~ 220
5 x 6
~ 260
~ 300
Safety
(V)
fuses (A)
400
3x100A
400
3x100 A
400
3x125 A
400
3x125 A
400
3x160 A
400
3x200 A
400
3x240 A
7
15
16
14
21
Alternative
heating (m²)
~ 70
~ 70
~ 100
~ 100
~ 150
~ 150
~ 210
~ 250
~ 310
~ 360
~ 400
Power cord
(mm²)
5x35
5x50
5x50
5x50
5x70
5x95
5x120

Hide quick links: