Feb. 12 INDEX OVERVIEW............................6 AVAILABLE MODELS........................6 IDENTIFICATION OF THE MACHINE....................6 MARKING............................7 PACKAGING AND TRANSPORT ......................7 PACKAGING ............................7 AVAILABLE VERSIONS........................8 AVAILABLE ACCESSORIES......................8 POSSIBLE COMBINATIONS......................9 DIMENSIONS ..........................10 ASSEMBLY OF THE MACHINE......................12 ASSEMBLY OF VERSION UC12 ....................13 ASSEMBLY OF VERSION UC13 ....................13 ASSEMBLY OF VERSION UC122 ....................14 ASSEMBLY OF VERSION UC123 ....................14 ASSEMBLY OF VERSION UC12 ....................15...
Page 4
Feb. 12 FUSES .............................30 ORDINARY MAINTENANCE......................31 FILTER MAINTENANCE........................31 7.1.1 Washing the filters ........................32 GENERAL INSPECTION OF THE FILTERS...................33 CLEANING THE MACHINE ......................33 EXTRAORDINARY MAINTENANCE....................34 SOSTITUTION OF ION EMITTER NEEDLES.................34 AVAILABLE VERSIONS........................35 NATURE SYSTEM ........................37 10.1 CONTROL PANEL ........................38 10.1.1 DISPLAY ...........................38 10.1.2 RECEIVER..........................38...
Page 5
Feb. 12 12.3 OPERATION OF THE MACHINE ....................55 12.4 INFRARED REMOTE CONTROL UNIT..................56 12.5 POWER SUPPLY AND ANTI BLACK-OUT SYSTEM ..............56 12.6 PURIFICATION ..........................56 12.7 SIGNALS ............................56 12.8 STATUS OF FILTRATION EFFICIENCY..................56 12.9 ELECTRONIC CIRCUIT ALARM SIGNALS ................56 TECHNICAL DATASHEETS......................58 CERTIFICATIONS ...........................58 14.1 CERTIFICATION C.N.R.
O V E R V I E W The air cleaner series UC1200 has been developed to improve the air quality in confined spaces. This machine has been specifically developed for use with modular ceiling systems, and comes with three distinct technology levels: Nature System, AFC System, Basic System.
Feb. 12 The tag shows the technical characteristics and serial number of the machine. Model Type Serial number In case technical assistance is requested, always supply model, type and serial number of the machine, -as can be read on the tag. 1.3 MARKING The CE conformity mark is shown on the tag.
Utilizing the available accessories the machine may be configured in eight distinct ways to provide maximum results. 3.1 AVAILABLE ACCESSORIES Num. CODE DESCRIPTION UC1200-00 Filter unit available in three This component is present in all configurations UC1200-01 technologies, additionally also UC1200-31 as satellite unit.
UC13 UC1200 with single outlet unit UC1200 with re oxygenising unit UC122 UC123 UC1200 with both outlet unit and re oxygenising unit UC1200 with two outlet units UC12s UC13s UC1200 with separate single outlet unit UC1200 with separate re oxygenising unit...
NATURE SYSTEM UNITA’ DI RIOSSIGENAZIONE MODELLO Unità di riossigenazione cod. UC1200-R UC1200-R cod. UC1200-B Nr 2 Bocchette ACCESSORI PER UC1200 cod. UC1200-B Nr 1 Bocchette cod. UC1200-C Nr 1 Coni di raccordo Ø250 Nr 1 Pannello raccordo Ø250 cod. UC1200-P Packing 670x370 cod.
Feb. 12 4.1 ASSEMBLY OF VERSION UC12 a) Open the packings and extract the components b) Remove the grill by pushing the black hatches towards the center c) Extract prefilter and electrostatic cell d) Position the outlet unit next to the filter unit (can be fixed to one side or the other) e) Using the included self threading screws Ø3,8x9 secure the air outlet unit to the filter unit Position the closure panel on the opposite side and secure using the same type of screws g) To facilitate the fixing to the ceiling we recommend leave filter and grill out...
Feb. 12 4.3 ASSEMBLY OF VERSION UC122 a) Open the packings and extract the components b) Remove the grill by pushing the black hatches towards the center c) Extract prefilter and electrostatic cell d) Position the outlet unit on the side of the filter unit e) Using the included self threading screws Ø3,8x9 secure the air outlet unit to the filter unit To facilitate the fixing to the ceiling we recommend leave filter and grill out ATTENTION: the...
Feb. 12 4.5 ASSEMBLY OF VERSION UC12s a) Open the packings and extract the components b) Remove the grill by pushing the black hatches towards the center c) Extract prefilter and electrostatic cell d) Position the Ø250 cone to the side of the filter unit (can be secured on both right and left side) e) Using the included self threading screws Ø3,8x9 secure the cone Ø250 to the filter unit Position the closure panel on the opposite side and using the same screws secure it to the filter unit.
Feb. 12 4.7 ASSEMBLY OF VERSION UC122s a) Open the packings and extract the components b) Remove the grill by pushing the black hatches towards the center c) Extract prefilter and electrostatic cell d) Position the Ø250 cones to the side of the filter unit e) Using the included self threading screws Ø3,8x9 secure the cones Ø250 to the filter unit Position the Ø250 panel on the outlet unit and secure using the included screws Ø3,8x9 g) To facilitate the fixing to the ceiling we recommend leave filter and grill out...
Feb. 12 I N S T A L L A T I O N The UC1200 is normally used in suspended ceiling systems. It is however also possible to install it with other ceilings, - masking it in false beams etc.
Page 18
Feb. 12 The outlets are equipped with curved foils with air directions. The particular design of the foils permits an optimal distribution pattern of the air, causing a so called "coanda" effect, also avoiding short circuiting in the centre area. Do not replace these outlets with models from other manufacturers. Outlet with curved foils used to optimize the air flow Outlet with curved foils Traditional outlet, -not recommended...
Feb. 12 5.2 INDICATIONS FOR CEILING The machine may be used with any type of ceiling. The dimensions are well suited for use in 600x600 ceiling raster systems of T-profile type, such as most commonly found on the market. The height of the machine requires at least 320mm space for proper installation. Automatikprodukter...
Feb. 12 5.3 FIXING IN CEILING The machine may be directly fixed to the ceiling with appropriate fasteners for the type of ceiling material. It is up to the individual installer to make sure that the fasteners are adequate for the intended use. The machine is supplied with a hole template in order to avoid errors The machine may be installed in two distinct ways : a) through use of external suspension brackets...
Feb. 12 5.3.1 Installation type A All the system components (filter unit, re oxygenising unit and outlet) are equipped with threaded inserts M6 to use with suspension bars. The brackets are supplied separate and must be mounted on the machine. Before proceeding with the installation, it is recommended to remove from the machine the inlet grill, filters and adjoining parts (outlet units, re oxygenising unit) in order to lower the machine weight.
Feb. 12 5.3.2 Installation type B FILTER UNIT Before proceeding with the installation, do the following : remove inlet grill by pressing the black hatches towards the centre remove the filters remove the grills of the outlets, pulling outwards (spring secured) Blanked holes a) On the ceiling side panel of the machine there are b) remove the internal plastic blanking plugs that...
12.5m minimum. For this reason the re oxygenising unit UC1200-R was created. The component, also having it's own ventilator, must be connected electrically to the filtering unit. This allows the re oxygenising unit fan speed to...
5.5 PILOT UNIT AND SATTELITE UNIT The UC1200 unit may control one or more remote units (denominated satellites). The satellites do not have their own electronic control circuitry but is controlled by the main unit. This solution reduces the overall cost of the investment, provided the interconnected machines may always work in the identical manner.
Feb. 12 5.6.2 Connection of re oxygenizing unit to a pilot unit The re oxygenizing unit may be mounted on the filter unit or separate. In both cases it is necessary to connect the fan motor of the re oxygenizing unit to the electrical terminals of the filter unit.
A pilot unit of type Basic System will control one remote filter unit and two re oxygenising units. In order to make this configuration a machine of type UC1200-01, UC1200-31 or UC1200-32 is used, joined to a machine without control circuit, denominated UC1200-00, identical for all technology versions. The electrical connection between the two is all that is needed.
Feb. 12 5.7.2 Connecting cables for power and micro switch The satellite unit is connected to the pilot unit for power and micro switch. For power, use normal 3G1.5 cable and proceed : 1) The pilot and satellite units must have contact plates as shown below and described previously. 2) Connect terminals 4-5-6 of the pilot unit to terminals 4-5-6 of satellite unit 1 Pilot unit contact plate Satellite unit contact plate...
Feb. 12 5.8 INSTALLED FILTERS 5.8.1 Metallic prefilter DIMENSIONS FILTER MODEL 115/3UC The metallic prefilter has the function of containing the larger particles present in the air. During operation the prefilter must always be in place. For maintenance operations, please take care not to bend or deform the prefilter.
Feb. 12 5.9.1 Ionizing wires The wires must be always integral and taut. In case of eventual breakage of one of them proceed immediately with its changing. 5.9.2 Capitation blades The blades must be at sight straight, without undulations. The blades must be also clean, without any strange particles among them.
Feb. 12 6.3 FUSES To access the electrical fuse proceed as follows : remove power remove the inlet grill as described previously open the fuse holder Replacement of defect fuses must be done by qualified personnel using fuses with same characteristics. Fuse holder Automatikprodukter...
Feb. 12 O R D I N A R Y M A I N T E N A N C E 7.1 FILTER MAINTENANCE In order to clean the filters, they should be extracted from the machine as follows: Fixing bracket 2) The filter cell is locked in place by two fixing 1) After having disconnected power, remove the inlet brackets.
Feb. 12 7.1.1 Washing the filters Filter maintenance is important both for the correct operation of the machine and for constant performance with the passage of time. The following materials are required for maintenance: 1) Two plastic trays, one with the bottom raised 2-3 cm for decanting the dirt. As an alternative to the raised bottom, use a stainless steel frame.
Feb. 12 d) remove the cell and leave it to dry in a warm place, keeping it raised from the ground by wooden strips (ovens with a maximum temperature of 60°C are tolerated). e) examine the state of the ionisation wires, stretching them slightly to check their mechanical strength. Use a cotton flock and methylated spirits to remove any residual traces of dirt.
Feb. 12 E X T R A O R D I N A R Y M A I N T E N A N C E It is recommended to have the machine inspected by qualified personnel once a year (normally during the summer season).
Feb. 12 A V A I L A B L E V E R S I O N S The SINTESYS line is manufactured in tree versions. For distinguishing which version you have, you should control the label placed outside on the machine or to check the control panel. ®...
Page 36
Feb. 12 ® AFC SYSTEM is the Top version of Environmental Air Purifiers and is using a digital technology for the controlling of its functions. The operations carried out by this machine are reported in the following definitions: ® AFC SYSTEM Identifies the method used by the microprocessor of the machine to gesture in complete autonomously way the parameters of the filtration, depending from the chosen performance of function and the level of saturation of the electrostatic cell.
Feb. 12 N A T U R E S Y S T E M The NATURE SYSTEM® is composed of the following elements: ® Electronic control of environmental revitalisation (rivitalizzazione ambientale The System automatically carries out all the controls and gives the commands to the Environmental Revitalisation along with the information required on the operating status of the apparatus.
Feb. 12 10.1 CONTROL PANEL All information regarding the operating status of the machine is displayed on the control panel. The control panel allows the user to: - select the air flow - activate/deactivate environmental revitalisation - turn off any alarms indicating apparatus malfunctions - constantly control all the functions relating to operation (air flow, environmental revitalisation, filtration efficiency, alarm situation).
Feb. 12 10.1.3 MANUAL, TEST, ON-OFF FILTER AND RESET BUTTONS The MANUAL button allows the air flow to be modified manually (0-1-2-3); the setting is memorised and maintained even if there is a power failure. The machine can be turned off by turning to flow 0 (fan off). Pressing the button indicated, a test on the operation of the electronic circuit signals is carried out.
Feb. 12 10.1.5 FILTERING STATUS The three Leds indicate the state of filtering efficiency and therefore only go on when filtration is activated; only one Led lights up at a time. The indications on filtering status are: - MAINTENANCE saturated filter to be cleaned or replaced (red Led): (maintenance);...
Feb. 12 ® 10.4 ENVIRONMENTAL REVITALISATION (RIVITALIZZAZIONE AMBIENTALE The Revitalizer revitalises the air in a confined environment in a completely automatic manner and until the pollutant has been completely cleaned from the environment. This phase is automatically activated after the complete purification of the air so that the phenomenon of electrostatic charging of the pollutants cannot occur as they would be deposited on the walls, on the furnishings and in the respiratory tract.
Feb. 12 10.7 NIGHT-TIME REVITALISATION WITH ENVIRONMENTAL DEODORIZATION If the Revitalizer is off or in flow position 2 or 3, this phase is activated by pressing button 1 of the infrared remote control unit three times consecutively, while if the flow is 1, the button should be pressed twice. During this phase, night revitalisation is signalled by the flashing of the yellow ION-ON and FILTER ON leds, and must only be used during the period when the premises are not occupied by people.
Feb. 12 10.10 OPTIMAL APPLICATION OF THE REVITALIZER NATURE SYSTEM® guarantees restoration of the conditions of purity and ionic re-equilibrium in all contaminated environments. You get the maximum results with NATURE SYSTEM® if you first identify the particular type of problem the Revitalizer must solve. For this reason, eight types of Revitalizer suitable for specific applications have been defined.
Feb. 12 10.11 ELECTRONIC CIRCUIT ALARM SIGNALS The electronic circuit detects every cause of imperfect air filtration. If there is a slight drop in the efficiency of the machine, the yellow PRE-ALARM Led will light up. If, however, the drop in efficiency is greater, filtering will be blocked completely and the red MAINTENANCE Led will go on.
Feb. 12 10.12 ELECTRONIC CIRCUIT ANOMALOUS SIGNALS In some cases signals such as the following may occur: - the display goes off momentarily, - the letter ‘P’ on the display goes on, - the letter ‘N’ on the display goes on. The first case is the automatic circuit protection tripping when ionisation voltage has been discharged to the earth.
Feb. 12 A F C S Y S T E M ® AFC SYSTEM The system automatically carries out all the controls and gives the commands to the high-efficiency filtration along with the information required on the operating status of the apparatus. Infrared remote control unit The remote control unit allows the user to control the operation of the machine from a distance of about 6÷7 metres;...
Feb. 12 11.1 CONTROL PANEL All information regarding the operating status of the machine is displayed on the control panel. The control panel allows the user to: - select the air flow - turn off any alarms indicating apparatus malfunctions - constantly control all the functions relating to operation (air flow, filtration efficiency, alarm situation).
Feb. 12 11.1.3 MANUAL, TEST, ON-OFF FILTER AND RESET BUTTONS The MANUAL button allows the air flow to be modified manually (0-1-2-3); the setting is memorised and maintained even if there is a power failure. The machine can be turned off by turning to flow 0 (fan off). Pressing the button indicated, a test on the operation of the electronic circuit signals is carried out.
Feb. 12 11.3 FILTERING STATUS The three Leds indicate the state of filtering efficiency and therefore only go on when filtration is activated; only one Led lights up at a time. The indications on filtering status are: - MAINTENANCE saturated filter to be cleaned or replaced (red Led): (maintenance);...
Feb. 12 11.6 PURIFICATION The Air Purifier purifies the air by means of a high-efficiency electrostatic filter whose operation is governed by an electronic circuit which guarantees optimal and constant performance with time in any situation. 11.7 SIGNALS The electronic control of this apparatus provides the user visually with all the information on operation required for correct use, and makes available the means for fast checking to seek any small anomalies, by means of the RESET - TEST - ON/OFF FILTER buttons.
Feb. 12 11.9 ELECTRONIC CIRCUIT ALARM SIGNALS The electronic circuit detects every cause of imperfect air filtration. If there is a slight drop in the efficiency of the machine, the yellow PRE-ALARM Led will light up. If, however, the drop in efficiency is greater, filtering will be blocked completely and the red MAINTENANCE Led will go on.
Feb. 12 11.10 ELECTRONIC CIRCUIT ANOMALOUS SIGNALS In some cases signals such as the following may occur: - the display goes off momentarily, - the letter ‘P’ on the display goes on, - the letter ‘N’ on the display goes on. The first case is the automatic circuit protection tripping when ionisation voltage has been discharged to the earth.
Feb. 12 B A S I C S Y S T E M BASIC SYSTEM The System carries out the controls and gives the commands for filtration and negative ionisation along with the information required on the operating status of the apparatus. Infrared remote control unit The remote control unit allows the user to control the operation of the machine from a distance of about 6÷7 metres;...
Feb. 12 12.1 CONTROL PANEL For modifying the operating status of the machine it is possible to use the control panel or the remote control. All information regarding the operating status of the machine is displayed on the control panel. The control panel allows the user to: - select the air flow - control of all the functions relating to operation (air flow, filter on, alarm situation).
Feb. 12 12.2.2 MANUAL AND ON-OFF FILTER BUTTONS The MANUAL button allows the air flow to be modified manually (OFF-1-2-3); the setting is memorised and maintained even if there is a power failure. The ON/OFF button is for activating/deactivating the filtration function and the negative ionisation.
Feb. 12 12.4 INFRARED REMOTE CONTROL UNIT The remote control unit allows you to control the machine, modifying the air flow from a distance of about 6-7 metres. The following functions are provided: - 1st FAN SPEED key: sets the “maintenance” flow (room half empty) - 2nd FAN SPEED key: sets the “normal use”...
Page 57
Feb. 12 The electronic circuit will light up an eventually block of filtration. The causes often can be resolved by a small operation. TYPE OF ALARM CAUSE OPERATION electrostatic cell dirty carry out normal maintenance electrostatic cell not properly clean if small dirty areas have remained, washing must be carried out again electrostatic cell damp...
V - Hz cells installation control speed 750 UC1200 speed 230 – 50 depending ceiling version 1100 speed 1450 RE OXYGENISING UNIT UC1200-R model capacity m Watt Power. Dimensions n° type of remote V - Hz cells installation control speed 170...