Mitsubishi Electric MSZ-GA50VA Service Manual page 16

Hide thumbs Also See for MSZ-GA50VA:
Table of Contents

Advertisement

9-4. Troubleshooting check table
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.
Abnormal
No.
Operation indicator lamp
point
Left lamp flashes.
0.5-second ON
Mis-Wiring
or serial
1
signal
0.5-second OFF
Indoor coil
Left lamp flashes.
thermistor
2-time flash
2
Room
tempera-
2.5-second OFF
ture
thermistor
Left lamp flashes.
3-time flash
Indoor fan
3
motor
2.5-second OFF
Left lamp flashes.
Indoor
4-time flash
control
4
system
2.5-second OFF
Left lamp flashes.
5-time flash
Outdoor
power
5
system
Left lamp flashes.
6-time flash
Outdoor
6
thermistors
Left lamp flashes.
7-time flash
Outdoor
control
7
system
Left lamp flashes.
14-time flash
Other
8
abnormality
2.5-second OFF
Lighted
· Flashing of OPERATION INDICATOR lamp (left-hand side lamp)
indicates abnormalities.
Blinking
Not Lighted
Symptom
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
Condition
When serial signal from outdoor unit is not
received for a maximum of 6 minutes.
When the indoor coil or room temperature
thermistor is short or open circuit.
When rotational frequency feedback signal is
not emit during indoor fan operation.
When it cannot properly read data in the
nonvolatile memory of indoor electronic
control P.C. board.
When it consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection witth in 1 minute
after start-up.
Outdoor thermistors short or open circuit
during compressor operation.
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.
An abnormality other than above mentioned is
detected.
16
Correspondence
• Refer to 9-6.D "How to check
mis-wiring and serial signal
error".
• Refer to 9-7.the
characteristics of indoor coil
thermistor, and the room
temperature thermistor.
• Refer to 9-6.A "Check of
indoor fan motor".
• Replace the indoor electronic
control P.C. board.
• Refer to "How to check of
inverter/compressor".
Refer to outdoor unit service
manual .
• Check the stop valve.
• Refer to "Check of outdoor
thermistor".
Refer to outdoor unit service
manual.
• Replace the inverter P.C.
board or the outdoor
electronic control P.C. board.
Refer to outdoor unit service
manual.
• Confirm the abnormality in
detail using the failure mode
recall function for outdoor unit.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msz-ga71vaMsz-ga60vaMsz-ga80va

Table of Contents