Mitsubishi Electric MSZ-GA50VA Service Manual page 14

Hide thumbs Also See for MSZ-GA50VA:
Table of Contents

Advertisement

2. Indoor unit failure mode table
Left lamp of
Abnormal point
OPERATION
(Failure mode)
INDICATOR lamp
Not lighted
Normal
Room temperature
1-time flash
thermistor
every 0.5-second
2-time flash
Indoor coil thermistor
2.5-second OFF
3-time flash
Serial signal
2.5-second OFF
11-time flash
Indoor fan motor
2.5-second OFF
12-time flash
Indoor control system
2.5-second OFF
NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (9-4.).
Condition
When the room temperature thermistor
short or open circuit is detected every 8
seconds during operation.
When the indoor coil thermistor short or
open circuit is detected every 8 seconds
during operation.
When the serial signal from the outdoor unit is
not received for a maximum of 6 minutes.
When the rotational frequency feedback
signal is not emitted during the 12-seconds
indoor fan operation.
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
14
Correspondence
Refer to the characteristics of the room
temperature thermistor (9-7.).
Refer to the characteristics of the main
indoor coil thermistor, the sub indoor coil
thermistor (9-7.).
Refer to 9-6.D "How to check mis-wiring
and serial signal error".
Refer to 9-6.A "Check of indoor fan
motor".
Replace the indoor electronic control
P.C. board.