UTICA BOILERS 95M-200 Control Manual And Troubleshooting Manual page 17

Hide thumbs Also See for 95M-200:
Table of Contents

Advertisement

SOFT LOCKOUT (Display flashes "9" and then "b" in first position; last two digits on steady (code))
Code
Reason For Soft Lockout
WARNING: Electrical shock hazard. Turn off power to boiler when working with wiring or replacing any boiler component.
High Limit Operation: Return temp.
24
is higher than supply temp.
25
High limit operation: outlet water
temp. increased too quickly.
Non-adjustable default setting
9.8°F/sec
26
aquastat contacts open
or
LWCO contacts open
or
3.5" Switch open
Blower turning when it should be off.
29
High limit operation: Temp. rise
30
across boiler too high.
61
Pressure switch contacts closed.
65
Blower not operating when turned
on.
VIII - TROUBLESHOOTING
Corrective Actions (pressing RESET should restart boiler immediately):
Verify boiler and system are full of water.
1
Make sure system does not have trapped air.
Inspect and verify system piping and components.
Make sure water flow is not reversed or pipes crossed.
Use contact thermometer to check return water temp. Compare to temp. shown with
2
display in "INFO" mode ("2" in first digit). Replace return temp. sensor if results are
not close. Replace control module if sensor replacement doesn't solve problem.
This usually indicates flow rate too low. Check system for:
1
Verify boiler and system are full of water.
Make sure system does not have trapped air.
Inspect and verify system piping and components.
Verify piping agrees with boiler manual recommendations.
Verify operation of boiler circulator:
2
Check voltage at circulator junction box to ensure 120 vac when boiler oper-
ates. if no voltage, check wiring and wiring connections.
High voltage terminal strip terminals 5 and 6 should show 120 vac for space
heating; terminals 3 and 4 should show 120 vac for DHW. Replace circulator if
powered but not operating.
Replace line voltage wire harness if necessary. Replace control module if wire
replacement doesn't resolve.
1
Verify proper setting of control.
Water temp too high, wait for temperature to drop below 180 degrees.
Check water level in boiler, fill if low.
2
Press LWCO reset switch on display panel
If problem still exists, check LWCO probe and board according to manufacturer's
instructions. replace if necessary.
Check pressure switch for proper operation. Replace if moisture has entered switch.
3
Check venting for blockage. Clear if present.
Check boiler wiring against wiring diagram. Replace line voltage and low voltage
1
wiring harnesses if necessary. Replace control module if wire replacement doesn't
resolve.
This usually indicates flow rate too low. Check system for:
1
Verify boiler and system are full of water.
Inspect and verify system piping and components.
Verify piping agrees with boiler manual recommendations.
Make sure system pressure drop is not too high.
Verify operation of boiler circulator.
2
Check voltage at circulator junction box to ensure 120 vac when boiler
operates. if no voltage, check wiring and wiring connections.
High voltage terminal strip terminals 5 and 6 should show 120 vac for space
heating; terminals 3 and 4 should show 120 vac for DHW. Replace circulator
if powered but not operating.
Replace line voltage wire harness if necessary. Replace control module if wire
replacement doesn't resolve.
Check pressure switches for proper operation. Replace pressure switch if moisture
1
has entered switch.
Turn off power to boiler. Remove line voltage connector at blower. Restart boiler
1
and check voltage across blower plug terminals. If 120 vac is NOT present, inspect
wiring and tightness of connections. replace line voltage wire harness if necessary.
Replace control module if wire harness replacement doesn't resolve.
If 120 vac is present on blower wire harness, replace harness and retry. If problem
2
persists, replace blower motor.
17