5) Calibration
Interface
6) Other settings (available on all operation modes)
Interface

3-7-2-6. Alarm page

This page records and displays the faults or warning events happened in history.
4 . T R O U B L E S H O O T I N G
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14
Description
1. Batt: Calibrate the battery voltage measurement. Calibration range is from 0V to 5.7V.
The default value is 0V. It is available on all operation modes.
2. Inv: Adjust the inverter output voltage; the adjustable range is from 0V to 6.4V, the
default value is 0V. It is only available in line / battery / converter mode;
3. Chg: Adjust the Charger output voltage; the adjustable value is from 0V to 6.9V, the
default value is 0V. It is only available in bypass / line / ECO /converter mode.
(NOTE: Before making charger output voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage; Be careful that the adjustment should
be suitable to battery specifications, or the battery maybe destroyed.)
Description
Hot standby:
Enable: Hot standby function is enabled. It means that the current UPS is set to
be host of hot standby system, and it will automatically restart after AC recovery
even without battery connected.
Disable: Hot standby function is disabled. The UPS is running at normal mode
and can't restart without battery.
Disable is default setting.
Backup Time Parameters Setting:
Batt Groups: Set the number of battery group ranging from 1 to 6. The default value is 1
group;
Batt Cap: Set the battery capacity such as 7AH, 9AH, 10AH, 12AH, 17AH, 26AH, 40AH,
65AH, 100AH and so on. The default value is 9AH.
Factor: Calibrate the displayed backup time by adjusting this multiplier factor. The
formulation is listed below:
Displayed backup time=Original calculated backup time × Multiplier factor
The value of default factor is 1.0, and it ranges from 0.5 to 2.
These parameters are for the battery backup time calculation
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
23