Electrical Connections - Vector OPA-S Operation Manual

Intelligent transmitters

Advertisement

Installation
1. Install the mounting plate straight to the wall or the flush mounting box. Make sure that the nipple with
the front holding screw is facing to the ground. Make sure the screw heads do not stand out more than
5 mm of the surface of the mounting plate.
2. Connect the wires of the terminals to the communication wires according wiring diagram
3. Slide the two latches located on the top of the front part into the hooks of the mounting plate.
4. Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make
sure the connection cable does not get into the way.
5. Tighten the front holding screw to secure the front part to the mounting plate.
Connection to Base Unit
Max. Distance: 50 m using shielded copper wire
Always use shielded copper wire if distance > 20 m and electro magnetic interference is present.
Setting of configuration parameters
Intelligent sensors can be adapted to fit perfect into your application. The preparation of the sensing signal is
defined by parameters.
The parameters are password protected. The parameters can be changed as follows:
1. Press UP and DOWN key simultaneously for three seconds. The display will indicate CODE.
2. Select a password using UP or DOWN keys. Dial 0009 in order to get access to the configuration
parameters. Press the RIGHT key after selecting the correct password.
3. Once logged in, choose IP for input configuration or OP for output configuration using UP or DOWN.
Press the RIGHT key after selection.
4. The parameters are now displayed. The small digits show the parameter number, the large one its value.
5. Select the parameters with the UP/DOWN keys. Change a parameter by pressing the RIGHT key. The
MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP and
DOWN key to adjust the value.
6. After you are done, press RIGHT or LEFT key in order to return to the parameter selection level.
7. Press the LEFT key again so as to leave the menu. The unit will return to normal operation if no key is
pressed for more than 5 minutes.
8. The parameters and its values depend on the transmitter. Please use the respective datasheet for the
list of parameters

Electrical connections

Normal cables maybe used for wiring in an EMC-save environment. In an extremely impaired EMC environment
use only shielded cables.
The operating voltage must comply with the requirements for safety extra-low voltage (SELV) as per
EN 60 730. Connect the cable using the four-pin plug provided.
Doc: 70-07-0171, V1.3: 20100421
Subject to alteration