Please note exhaust gas flue connetor for ODW-180 & 199 is
on the opposite side from ODW-099 & 120 (Reference : Page 8 & 9)
Other venting option #5 (Vertical Venting)
1.
ODW-099B ~ 120B : 3" Schedule 40 PVC
ODW-180C ~ 199C : 3" Schedule 40PVC
4. Minimum pipe length of 10ft is recommended to prevent freezing
air entering the unit in cold climate.
4 ½" for 099~120
6" for 180~190
2 x 45 Deg Fittings
ODW Model
#4 (Snorkel flue)
4" Schedule 40 PVC
( one elbow is equal to 5ft length )
See table 1 below.
Minimum 12" from bottom of intake to roof line
ㆍStandard Venting rules apply
ㆍAttach Flue and Intake pipes to unit with
PVC Cement approved for this type of application
ㆍAttach Vent Termination to Flue Pipe and
caulk around joint to ensure seal
Model
ODW-099~120B
ODW-180~199C
57
Vent Size
Max. Flue Length
Equivalent Length
3" PVC
45 feet
3" PVC
38 feet
4" PVC
45 feet
Table 1.