LG FM15AH UL3 Svc Manual page 99

Multi air conditioner, multi-inverter type
Table of Contents

Advertisement

5. Trouble Shooting
Display
Title
code
DC Compressor
26
Position
I Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
Yes
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
Yes
Is compressor
Wire connection
condition normal?
Yes
Is inverter PCB assembly normal?
Yes
Recheck power and installation condition
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Compressor
Starting fail error
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
No
operation
4. Check refrigerant pressure
¡ Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
(0.188 ±7%)
No
2. Check insulation resistance between compressor
terminal and pipe (over 50MΩ )
¡ Replace compressor if abnormality found
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
No
3. Check compressor terminal connection condition
(bad contact)
¡ Reassemble if abnormality found
Check inverter PCB assembly IPM normality
No
¡ Replace inverter PCB assembly
- 98 -
Check point & Normal condition
• Check the connection of comp wire "U,V,W"
• Malfunction of compressor
• Check the component of "IPM", detection parts.
LGE Internal Use Only