Magic-pac MHP4 Series Installation And Maintenance Instructions Manual page 6

Advertisement

Model
MHP4-9-12
MHP4-9-18
MHP4-9-24
MHP4-9-30
MHP4-9-36
MHP4-10-18
MHP4-10-24
MHP4-10-30
Condensate Drain
Provisions must be made to properly drain the indoor and
outdoor drain pans of this appliance.
Indoor drain connection: 1/2" NPT to 3/4" PVC fitting (schedule
40). Outdoor drain connection: 3/4" NPT to 3/4" PVC fitting
(schedule 40). Both drains must be trapped as shown in Figure
5. The drain line should pitch gradually downward at least 1"
per 10' of horizontal run to open drain.
CAUTION
Use thread sealant on the threaded fittings. Install
threaded fittings by hand only. Do not over torque the
fittings.
Do not thread metal condensate fittings to unit drain
pan.
If local codes require the use of metal condensate lines, do
not thread metal fittings into the unit drain pan. A 1/2" x 3/4"
threaded plastic nipple is available from the manufacturer as
Page 6 of 18
Blower Performance
Blower
Speed
Low
Medium/Low
Medium/High
High
Low
Medium/Low
Medium/High
High
1075
Low
Medium/Low
1000
Medium/High
1100
High
1270
Low
Medium/Low
Medium/High
High
Low
Medium/Low
Medium/High
1070
High
1220
Table 3
Issue 0941
External Static Pressure (in.w.c. w/filter)
0.1
0.2
450
440
700
690
810
800
940
920
620
600
840
820
975
940
1000
750
720
980
1080
1230
450
440
690
700
810
800
940
920
630
620
900
890
1030
1150
Condensate Drain Installation
0.4
0.3
425
400
650
680
790
770
875
850
580
560
785
750
825
870
930
880
680
650
950
920
1050
1020
1200
1170
425
400
680
650
790
770
850
875
610
580
850
800
920
1000
1100
1030
Figure 5
0.5
370
600
730
810
535
700
760
800
620
880
980
1130
370
600
730
810
550
750
840
920
506325-01

Hide quick links:

Advertisement

loading