INSTALLATION

General
These instructions explain the recommended method of
installation of the MHP4 heat pump unit and associated
electrical wiring.
This unit is designed and approved for use as a self-
contained air to air heat pump system.
These instructions, and any instructions packaged with
mating components and/or accessories, should be carefully
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
These instructions are intended as a general guide only, for
use by qualified personnel and do not supersede any national
or local codes in any way. Compliance with all local, state,
provincial, or national codes pertaining to this type of equipment
should be determined prior to installation.
Inspection
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted on
the carrier's freight bill. Take special care to examine the
unit inside the carton if the carton is damaged. File a claim
with the transportation company. If any damages are
discovered and reported to the carrier do not install the
unit, as claim may be denied.
Check the unit rating plate to confirm specifications are
as ordered.
Application Limitations
Outdoor Ambient Air Temperature °F
Minimum DB
Cool
65
Indoor Ambient Air Temperature °F
Minimum
DB/WB
DB
Cool
Heat
62/57
50
Page 2 of 18
Maximum DB
Cool
Heat
115
75
Maximum
DB
DB/WB
Heat
Cool
80
90/72
Table 1
Limitations
The unit should be installed in accordance with all national
and local safety codes.
Limitations of the unit and appropriate accessories must also
be observed.
The outdoor fan is designed to operate against no more
than .10" W.C. static pressure.
Minimum and maximum operation conditions must be
observed to assure maximum system performance with
minimum service required. Refer to Table 1 for the
application limitations of the unit.
Location
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
For information on wall sleeves and grille accessories, see
ACCESSORIES beginning on page 11.
The design is certified for thru-the-wall or up-to-the wall
(inside wall) installation only. The interior portions of the unit
may be surrounded by a closet with clearances to
combustible material held to 0" at the sides, top, and front of
the plenum. All servicing and cleaning of the unit can be
performed from the front. If installed in a closet or utility room,
provide 25" clearance in front for service if the door to the
room is not in line with the front of the unit (see Figure 1).
Accessibility clearances must take precedence over fire
protection clearances.
The outside of the unit may be flush with the face of the
exterior wall, and it should not be obstructed with trees,
landscape materials, or building structure. Unit can be
installed recessed with appropriate wall sleeve accessories.
There is no minimum clearance required on locating the
unit to an interior corner of a building.
If the unit is installed in a residential garage, it must be located
or protected to avoid physical damage by vehicles. The unit
must be installed so that no electrical components are
exposed to water.
This unit must be installed level to allow for proper
drainage of the unit base pan and indoor drain pan.