Download Print this page
Hitachi RAS-SD10CCT Installation Manual
Hitachi RAS-SD10CCT Installation Manual

Hitachi RAS-SD10CCT Installation Manual

Split indoor/outdoor unit
Hide thumbs Also See for RAS-SD10CCT:

Advertisement

FOR SERVICE PERSONNEL ONLY
HITACHI SPLIT-UNIT AIR CONDITIONER
INSTALLATION MANUAL
Indoor Unit
Outdoor Unit
RAC-SD10CCT
RAS-SD10CCT
RAC-SX10CCT
RAS-SX10CCT

SAFETY PRECAUTION

Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of
operating the unit as described in the user's guide.
Please request your sales agent or qualiÀ ed technician to install your unit. Water leakage, short circuit or À re may occur if
you do the installation work yourself.
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and À re.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
Be sure to use the speciÀ ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and À re.
Please use the speciÀ ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and À re may occur.
Be sure to use the speciÀ ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only speciÀ ed refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a
rupture may be caused.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with À re, a poisonous
gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with À re in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modiÀ cations to the air conditioner may be dangerous. If a breakdown occurs please call a qualiÀ ed air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and À re, etc.
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock
exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
Do not install the unit near a location where there is Á ammable gas. The outdoor unit may catch À re if
Á ammable gas leaks around it.
Do not install the indoor unit in a machine shop or kitchen where vapor from oil or its mist Á ows to the indoor unit. The oil
O
will deposit on the heat exchanger, thereby reducing the indoor unit performance and may deform and in the worst case,
break the plastic parts of the indoor unit.
Please ensure smooth Á ow of water when installing the drain hose.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
The draining of the water container inside the indoor unit can be done from the left.
Therefore the mounting plate must be À xed horizontally or slightly tilted towards the
side of drain hose. Otherwise, condensed water may overÁ ow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the mounting plate.
Procedures of Installation and Precautions
Procedures to À x the mounting plate.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Procedures to À x the holder of remote control.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall Penetration and Installation of Protection Pipe
Drill a ø 65mm hole on
wall which is slightly tilted
towards the outdoor side.
Drill the wall at a small
angle.
Cut the protection pipe
according to the wall
thickness.
Empty gap in the sleeve
of protection pipe should
be completely sealed with
putty to avoid dripping of
rain water into the room.
<
>
IA1018: A
Carefully read through the procedures of proper
installation before starting installation work.
The sales agent should inform customers regarding
the correct operation of installation.
Tools Needed For Installation Work
+ –
Screwdriver
Measuring Tape
Saw
Pipe Cutter
Hexagonal Wrench Key (
Power Drill (ø 65mm ~ ø 80mm)
Pliers or Wrench
Torque Wrench
Pump Adaptor
Flare Tool
Gas Leakage Detector
Manifold Valve
Charge Hose
Reammer
WARNING
CAUTION
2
Installation of the Indoor Unit
VERTICALLY DOWNWARD PIPING
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain
hose.
Installation
The upper part of the indoor unit is hanged on the mounting plate.
The projection at the lower part of the indoor unit is hooked onto the mounting plate.
HORIZONTAL PIPING
Preparation
Change of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap during horizontal piping as shown
in À gure below. Be sure to plug in the drain hose until the insulating material folds
upon itself.
Please use pliers to pull
3. Fix the mounting plate on wall
out the drain cap.
with 4.1 x 32 screw
(This is an easier way to
(As shown in À gure below)
remove the drain cap).
Remove the cap for
drain hose installation
WARNING
Be sure that the wire is not
in contact with any metal
in the wall. Please use
the protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
dew may drop.
CAUTION
THE CHOICE OF MOUNTING SITE
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
No nearby heat source and no obstruction near the air outlet is
allowed.
The clearance distances from top, right and left are speciÀ ed in
À gure below.
Knife
The location must be convenient for water drainage and pipe
4mm)
connection with the Outdoor unit.
Vacuum Pump
To avoid interference from noise please place the unit and its
remote controller at least 1m from the radio, television and inverter
Vacuum
type Á uorescent lamp.
To avoid any error in signal transmission from the remote controller,
File
please put the controller far away from high-frequency machines
and high-power wireless systems.
The installation height of indoor unit must be 2.3m or more.
Names of Indoor Components
No.
Component's Name
Mounting Plate
1
Screw for Mounting Plate
2
( 4 . 1 x 3 2 )
Holder for Remote
Controller
3
AAA Size Battery
4
Screw for holder of Re-
mote Controller
5
( 3 . 1 x 1 6 )
Remote Controller
6
Purifying Filter
7
CAUTION
Please pull the lower
part of the indoor unit
outwards to check if
the unit is hooked onto
the mounting plate.
Improper installation
may cause vibration
and noise.
Condensed water
may leak out if not
inserted properly.
(Please note the following matters and obtain permission from customer before installation).
WARNING
The outdoor unit must be mounted at a location which can support
heavy weight. Otherwise, noise and vibration will increase.
CAUTION
Do not expose the unit under direct sunshine or rain. Besides, ventilation must
be good and clear of obstruction.
The air blown out of the unit should not point directly to animals or plants.
The clearances of the unit from top, left, right and front are speciÀ ed in À gure
below. At least three of the above sides must be open air.
Be sure that the hot air blown out of the unit and noise do not disturb the
neighbourhood.
Do not install at a location where there is Á ammable gas, steam, oil and smoke.
The location must be convenient for water drainage.
Place the outdoor unit and its connection wire at least 1m away from the
antenna or signal line of television, radio or telephone. This is to avoid noise
interference.
Do not install outdoor unit facing strong wind direction. It may damage the fan
motor.
Do not install the outdoor unit in a place where small animals may build their
nests. If small animal goes inside the unit and touches the electrical parts,
failure of the unit, smoke or À re may be caused. Request your customer to
keep the surrounding of the unit is clean.
Qty
Direction of Piping
Figure showing the Installation
of Indoor and Outdoor Unit.
1
T h e r e a r e 6 d i r e c t i o n s
allowed, namely, horizontally
In case the pipe length is more than the recommended length for
6
perpendicular to the unit,
chargeless, add refrigerant R410A as below. Do not exceed the
vertically down from right,
maximum pipe length.
horizontally out from right,
h o r i z o n t a l l y o u t t o l e f t ,
Model
horizontally out to right,
1
vertically down from left.
RAC-SD10CCT
RAC-SX10CCT
Dimension of Mounting Stand
of the outdoor unit
Be sure to
(unit : mm)
completely
2
seal any
gap with
putty.
2
1
2
INSTALLATION OF REFRIGERATING PIPES AFTER CONNECTION
The refrigerating pipes should be adjusted to fit
into the hole on the wall and then ready for further
connection.
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing electrical
cover. (Refer to "CONNECTION OF POWER CORD")
After adjustment, À t the connecting cord and pipes
into the space available under the indoor unit. Use
holder to hold them tight.
Holder can be attached at the either of 2 places.
Please select the easier position.
THE CONNECTION OF REFRIGERATING PIPE DURING THE
INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
arrangement are attached.
P
Installation
Hang the Indoor unit onto the mounting plate. Use the temporary
stand at the back of the Indoor unit to push its lower part
15cm forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover.
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the mounting plate.
Heat insulation pipe
Pull this to the front
during the connection
Connecting
of refrigerating pipes
cord
to ease task.
Refrigerating pipe
3
Installation of Drain Hose
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth Á ow of condensed water of the Indoor
CAUTION
unit during installation. (Carelessness may result in water leakage.)
WARNING
CAUTION
CAUTION
The installation height of indoor
unit must be 2.3m or more.
CAUTION
Max. Pipe Chargeless up to Additional R410A
20
8
20 gram/meter
20
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commercial
products).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
CAUTION
The rubber strap used for
À xing the insulator should
not be tied with great force.
Otherwise, this will damage
heat insulation and causes
water condensation.
CAUTION
Please À x in the plastic core
after Á aring to avoid plastic
chips entering the pipes.
CAUTION
Be sure that the
drain hose is not
loosely connected
or bend.

Advertisement

loading

Summary of Contents for Hitachi RAS-SD10CCT

  • Page 1: Safety Precaution

    The sales agent should inform customers regarding CAUTION CAUTION the correct operation of installation. HITACHI SPLIT-UNIT AIR CONDITIONER ● ● No nearby heat source and no obstruction near the air outlet is Do not expose the unit under direct sunshine or rain. Besides, ventilation must INSTALLATION MANUAL be good and clear of obstruction.
  • Page 2 CAUTION holder as shown in À gure beside. Reuse of piping R-22 model only apply if previous model is Hitachi and proper pump down method is used. Take out air conditioner unit. Install New Refrigerant Power Source And Operation Test...