Closed System/Thermal Expansion - A.O. Smith XVRL-40 Installation Instructions And Use & Care Manual

Residential gas water heaters
Table of Contents

Advertisement

HOT WATER
OUTLET
(DO NOT CAP OR PLUG)
1" MINIMUM
METAL
DRAIN PAN
DRAIN
UNTEMPERED
HOT WATER
HOT
WATER
OUTLET
IN A CLOSED SYSTEM USE A
THERMAL EXPANSION TANK
COLD WATER SUPPLY TO FIXTURES
PRESSURE REDUCING VALVE
WITH BYPASS
COLD WATER
INLET
COLD WATER INLET VALVE
(SHUT-OFF VALVE)
TEMPERATURE AND PRESSURE (T&P)
RELIEF VALVE (OPTIONAL TOP T&P
RELIEF VALVE NOT SHOWN)
DISCHARGE PIPE
MASSACHUSETTS: INSTALL
A VACUUM RELIEF IN COLD
DRAIN LINE
WATER LINE PER SECTION
3/4" ID
19 MGL 142.
MINIMUM
6" MAXIMUM
AIR GAP
FIGURE 13.
TEMPERED WATER
TO FIXTURES
COLD
WATER
INLET
TEMPERING VALVE
(SET TO 120°F)
FOLLOW THE TEMPERING
VALVE MANUFACTURER'S
INSTRUCTIONS
FIGURE 14.
Please note the following:
The system should be installed only with piping that is
suitable for potable (drinkable) water such as copper,
CPVC, or polybutylene. This water heater must not be
installed using iron piping or PVC water piping.
Use only pumps, valves, or fittings that are compatible
with potable water.
It is recommend that only full flow ball or gate valves
are used in water piping installations. The use of valves
that may cause excessive restriction to water flow is not
recommended.
Use only 95/5 tin-antimony or other equivalent solder.
Any lead based solder must not be used.
Piping that has been treated with chromates, boiler seal,
or other chemicals must not be used.
Chemicals that may contaminate the potable water
supply must not be added to the piping system.

Closed System/Thermal Expansion

Periodic discharge of the temperature and pressure relief valve
may be due to thermal expansion in a closed water supply
system. The water utility supply meter may contain a check valve,
backflow preventer or water pressure reducing valve. This will
create a closed water system. During the heating cycle of the
water heater, the water expands causing pressure inside the
water heater to increase. This may cause the temperature and
pressure relief valve to discharge small quantities of hot water. To
prevent this, it is recommended that a diaphragm-type expansion
tank (suitable for potable water) be installed on the cold water
supply line. The expansion tank must have a minimum capacity of
1.5 U.S. gallons for every 50 gallons of stored water. Contact the
local water supplier or plumbing inspector for information on other
methods to control this situation.