4. Disassembly and Reassembly
4-1 Compressor Replacement Flow Chart
Inspect electrical
wiring for defects, and
terminals for correct
and secure connections
Yes
Problem?
No
Corrective action
Add oil as necessary
Samsung Electronics
Locate cause of defect
Release refrigerant
Disconnect electrical wiring
from compressor
Cut refrigerant lines
from compressor
Plug disconnected lines
Replace compressor
Solder discharge line
Solder suction line
Check refrigerant oil level
Yes
Low oil level?
Use nitrogen gas
No
Perform soldering function
Fill system with nitrogen gas
Check for leakage
Yes
Leakage?
No
Release nitrogen gas?
Evacuate system
Recharge system
Pinch and braze filling tube