Specifications Of Electrical Parts - Toshiba RAV-SM564ATJP-E Service Manual

Air-conditioner (split type)
Table of Contents

Advertisement

*
RAV-SM564AT
P
No.
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
RAV-SM1104AT
*
No.
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
SVM-13072.indb 28
SVM-13072.indb 28

5. SPECIFICATIONS OF ELECTRICAL PARTS

*
*
*
, SM804AT
P
Parts name
P
*
, SM1404AT
*
P
*
Parts name
Type
DA150A1T-20F
3 phase, 4P, 1100 W
ICF-140-43-4R
Output 43 W
STF-H01AZ1724A1
PQ-M01012-000082
ACB-4UB83W
OFF:4.15MPa
CH-57-Z-T
10mH, 16A
MCC-1645
-
AC250 V, 25 A
-
AC250 V, 6.3 A
-
AC250 V, 3.15 A
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
50 kΩ at 25°C
-
50 kΩ at 25°C
CS-12AL
OFF: 125 ± 4°C, ON: 90 ± 5°C
Type
DA330A2T-20M
3 phase, 4P, 3000W
WDF-340-A100-1
Output 100 W
STF-H01AZ1724A1
CAM-MD12TF-18
ACB-4UB83W
OFF:4.15MPa
CH-62
6mH, 18.5A
MCC-1648
-
AC250 V, 25 A
-
AC250 V, 10 A
-
AC250 V, 3.15 A
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
50 kΩ at 25°C
-
50 kΩ at 25°C
CS-12AL
OFF: 125 ± 4°C, ON: 90 ± 5°C
– 28 –