Error Mode Detected By Outdoor Unit - Toshiba RAV-SM564ATJP-E Service Manual

Air-conditioner (split type)
Table of Contents

Advertisement

Error mode detected by outdoor unit

Check code
Indoor unit
Disconnection, short of discharge
F04
temp. sensor (TD)
Disconnection, short of heat exchanger
F06
temp. sensor (TE)
Disconnection, short of heat exchanger
F07
temp. sensor (TL)
Disconnection, short of suction temp.
F12
sensor (TS)
Miss-mounting of outdoor temp.
F15
sensor (TE, TS)
Disconnection, short of outside air
F08
temp. sensor (TO)
Disconnection, short of heat sink
F13
temp. sensor (TH)
F31
Outdoor EEPROM error
L10
Unset model type of service P.C. board
Heat sink overheat error
∗ Heat sink temp. sensor detected
P07
over specified temperature.
Detection of gas leak
∗ Discharge temp. sensor (TD),
P15
Suction temp. sensor (TS) detected
temperature over specified temp.
4-way valve inverse error
∗ After heating operation has started,
indoor heat exchanger temp. drops
P19
under the specified temp.
∗ After heating operation has started,
outdoor heat exchanger / suction
temp. rises over the specified temp.
Compressor break down
∗ Although operation has started,
H01
operation frequency decreases and
operation stops.
Compressor lock
H02
* Over-current detection after
compressor start-up
SVM-13072.indb 55
SVM-13072.indb 55
Operation of diagnostic function
Status of
Cause of errors
air conditioner
Stop
Stop
Stop
Stop
Stop
Continue
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
1. Check discharge temp. sensor (TD).
Displayed when
error is detected
2. Check outdoor P.C. board
1. Check heat exchanger temp. sensor (TE).
Displayed when
error is detected
2. Check outdoor P .C. board .
1. Check heat exchanger temp. sensor (TL).
Displayed when
error is detected
2. Check outdoor P.C. board .
1. Check suction temp. sensor (TS).
Displayed when
error is detected
2. Check outdoor P.C. board.
1. Check temp. sensor (TE, TS).
Displayed when
error is detected
2. Check outdoor P.C. board.
1. Check outside air temp. sensor (TO).
Displayed when
error is detected
2. Check outdoor P.C. board.
Displayed when
1. Check outdoor P.C. board
error is detected
Displayed when
1. Check outdoor P.C. board.
error is detected
Displayed when
1. Outdoor service P.C. board.
error is detected
Check model type setting jumper wire.
1. Check screw tightening between P.C. board and heat
Displayed when
sink and check radiator grease.
error is detected
2. Check heat sink blast path.
1. Check gas leak, recharge
2. Check full open of service valve.
Displayed when
3. Check PMV (Pulse Motor Valve).
error is detected
4. Check broken pipe.
5. Check discharge temp. sensor (TD), suction temp.
sensor (TS).
1. Check operation of 4-way valve.
2. Check outdoor heat exchanger (TE), suction temp.
sensor (TS).
Displayed when
error is detected
3. Check indoor heat exchanger sensor (TC).
4. Check 4-way valve coil.
5. Check PMV (Pulse Motor Valve).
1. Check power supply voltage. (50 Hz : AC 198 to 264 V,
Displayed when
60 Hz : AC 198 to 242 V)
error is detected
2. Overload operation of refrigerating cycle
1. Compressor problem (Lock, etc.): Replace compressor.
Displayed when
2. Compressor wiring error (Open phase)
error is detected
– 55 –
FILE NO. SVM-13072
Judgment and measures
11/01/13 1:53 PM