Typical Operating Conditions - Lennox EL195DF SERIES User Manual

Hide thumbs Also See for EL195DF SERIES:
Table of Contents

Advertisement

V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment1
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.
3 − Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in
OFF position.
B−Temperature Rise (Figure 51)
Temperature rise for EL195UH units depends on unit input,
blower speed, blower horsepower and static pressure as
marked on the unit rating plate. The blower speed must be
set for unit operation within the range of TEMP. RISE °F"
listed on the unit rating plate.
TEMPERATURE RISE
Supply Duct Temperature ________
Return Duct Temperature
Temperature Rise = ________
FIGURE 51
_
_____
SUPPLY
AIR
Temperatures
RETURN AIR
Page 40
C−External Static Pressure
1 − Tap locations shown in figure 52.
2 − Punch a 1/4" diameter hole in supply and return air ple-
nums. Insert manometer hose flush with inside edge of
hole or insulation. Seal around the hose with perma-
gum. Connect the zero end of the manometer to the
discharge (supply) side of the system. On ducted sys-
tems, connect the other end of manometer to the return
duct as above.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow-
er motor speed to deliver the air desired according to
the job requirements. For heating speed external static
pressure drop must not be more than 0.5" W.C. For
cooling speed external static pressure drop must not
be more than 0.8" W.C.
4 − Seal the hole when the check is complete.
EXTERNAL STATIC PRESSURE
Supply Duct Static ________
Return Duct Static + _____
Total Duct Static = ________
(dry coil)
Supply Air
FIGURE 53
D−Blower Speed Taps
Blower speed tap changes are made on the integrated con-
trol. See figure 4. The heating tap is connected to the
HEAT" terminal and the cooling tap is connected to the
COOL" terminal. On all units the continuous blower tap is
connected to the FAN" terminal. Unused taps must be se-
cured on two dummy terminals labeled "PARK. To change
out existing speed tap, turn off power and switch out speed
tap with tap connected to PARK". See blower speed tap
table on unit diagram for motor tap colors for each speed.
Duct Static
or
Return Air