Lennox EL195DF SERIES User Manual page 10

Hide thumbs Also See for EL195DF SERIES:
Table of Contents

Advertisement

Primary Limit Location and Heat Exchanger
Install limit face down
FIGURE 6
4. Gas Valve (GV1)
The EL195DF uses an internally redundant to valve to assure
safety shut-off. If the gas valve must be replaced, the same
type valve must be used.
24VAC terminals and gas control switch are located on
top of the valve. All terminals on the gas valve are con-
nected to wires from the ignition control. 24V applied to the
terminals opens the valve.
Inlet and outlet pressure taps are located on the valve. A
manifold adjustment screw is also located on the valve. An
LP/Propane changeover kit is available.
Gas Valve
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
(under
barbed
fitting)
INLET
PRESSURE
PORT
FIGURE 7
5. Flame Sensor (Figure 5)
A flame sensor is located on the left side of the burner sup-
port. The sensor is mounted on the bottom burner box plate
and the tip protrudes into the flame envelope of the left−
most burner. The sensor can be removed for service with-
out removing any part of the burners. During operation,
flame is sensed by current passed through the flame and
sensing electrode. The ignition control allows the gas valve
to remain open as long as flame signal is sensed.
NOTE − The EL195DF is polarity sensitive. Make sure that
the furnace is wired correctly and is properly grounded.
A microamp DC meter is needed to check the flame signal
on the integrated control.
Flame (microamp) signal is an electrical current which passes
from the integrated control to the sensor during unit operation.
Current passes from the sensor through the flame to ground to
complete a safety circuit.
To Measure Flame Signal − Integrated Control:
Use a digital readout meter capable of reading DC micro-
amps. See figure 8 for flame signal check.
1 − Set the meter to the DC amps scale.
2 − Turn off supply voltage to control.
3 − Disconnect integrated control flame sensor wire from
the flame sensor.
4 − Connect (−) lead to flame sensor.
5 − Connect (+) lead to the ignition control sensor wire.
6 − Turn supply voltage on and close thermostat contacts to
cycle system.
7 − When main burners are in operation for two minutes, take
reading.
6. Ignitor (Figure 5)
EL195DF units use a mini−nitride ignitor made from a pro-
prietary ceramic material. To check ignitor, measure its re-
sistance and voltage. A value of 39 to 70 ohms indicates a
good ignitor. Voltage to the ignitor should be 102VAC −
MANIFOLD
132VAC. See figure 9 for resistance and voltage checks.
PRESSURE
OUTLET
PORT
Page 10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents